_<strong>ASC2500</strong>_de_en_es_fr_ru.book Seite 95 Dienstag, 3. Mai 2011 10:24 10<strong>AirCon</strong> <strong>Service</strong> Center<strong>Service</strong> tasksINOTE5. Enter the password “2224”.6. Confirm “Pressure transducer” by pressing ENTER.7. Then follow the instructions in the display.• Unscrew the service couplings (12) and (13) from the servicehoses (10) and (11).• Use the keypad (7) to enter the current local atmospheric pressureand press ENTER to confirm.You can look up the current atmospheric pressure for your region on theInternet, for example at http://www.meteo24.de/wetter/ under “air pressure”.8. When calibration has been completed, press ENTER to exit the menu.9. Press STOP twice to access the standby menu.10. Screw the service couplings (12) and (13) hand-tight onto the servicehoses (10) and (11), taking care not to mix up the red and bluemarkings on the couplings and hoses.EN 95