Code Description Factory setting-:5 Hysteresis frequency reached (version V1.2 IE u 21) 0.3 HzAPI can be adjusted between 0 and 200 Hz.This parameter can be used to control the hysteresis of the function which determines if the drive hasreached the frequency reference. Increase this parameter if the drive is struggling to reach the"reference reached" state.If rFr (motor frequency) - FrH (frequency reference) < AP1 - 0.2 Hz, reference reached = 1If rFr (motor frequency) - FrH (frequency reference) > AP1, reference reached = 0Motor frequencySpeed referenceAP1AP1AP1- 0,2 0.2 HzENGLISHReference reachedtThis function is only active when the motor is running and the PI regulator is in operation.7