1.2 SerVICe ConDItIonS<br />

English<br />

open <strong>Circuit</strong> <strong>Breaker</strong><br />

Ambient temperature<br />

Operation: –5...40ºC, with an average in 24h of up to 35ºC. For application of the <strong>ABW</strong><br />

circuit breakers in environments with temperatures above 40°C, consider the maximum<br />

values of nominal current presented in the table below:<br />

Ambient<br />

temperature<br />

<strong>ABW</strong>16 <strong>ABW</strong>20 <strong>ABW</strong>25 <strong>ABW</strong>32 <strong>ABW</strong>40 <strong>ABW</strong>50<br />

40°C 1600 2000 2500 3200 4000 5000<br />

45°C 1600 2000 2500 3200 4000 5000<br />

50°C 1600 2000 2500 3200 4000 5000<br />

55°C 1550 2000 2450 3000 3900 4850<br />

60°C 1500 2000 2350 2900 3750 4700<br />

Storage: –20...60ºC, with average in 24h of up to 35ºC.<br />

Altitude of Installation<br />

≤ 2000m. For application of the <strong>ABW</strong> circuit breakers at altitudes above 2000m, apply<br />

the reduction factors of nominal voltage and current presented in the table below.<br />

Altitude - h<br />

reduction factor of<br />

nominal Voltage<br />

reduction factor of<br />

nominal Current<br />

h ≤ 2000m 1,00 1,00<br />

2000 < h ≤ 2600m 0,95 0,99<br />

2600 < h ≤ 3900m 0,80 0,96<br />

relative Humidity<br />

≤ 85% @ 40ºC.<br />

≤ 90% @ 20ºC.<br />

presence of gases<br />

H 2 S ≤ 0,01 ppm; SO 2 ≤ 0,01 ppm.<br />

<strong>ABW</strong> | 9