Fault probable Cause<br />

Undue<br />

activation<br />

of the<br />

protection<br />

unit<br />

Protection<br />

unit does not<br />

activate<br />

Insertion/<br />

removal is<br />

not possible<br />

Indicator<br />

and/or<br />

position lock<br />

do not work<br />

Contatos<br />

auxiliares<br />

não<br />

funcionam<br />

1. Incorrect settings of the<br />

protection functions.<br />

English<br />

open <strong>Circuit</strong> <strong>Breaker</strong><br />

Corrective Actions<br />

1st Alternative 2nd Alternative<br />

Set parameters correctly.<br />

2. Fault in the protection unit. -<br />

1. Poor contact in the<br />

connection to the internal<br />

TCs.<br />

2. Poor contact in the<br />

connection with the trip coil.<br />

Contact WEG<br />

technical<br />

assistance.<br />

Check status of the<br />

connections by means of the<br />

protection unit menus. Contact WEG<br />

Check activation by means<br />

of the test menu of the<br />

protection unit.<br />

3. Fault of protection unit. -<br />

1. Removal rod does not<br />

enter into the orifice.<br />

2. Removal rod does not<br />

turn.<br />

3. Claws of the removal<br />

carriage damaged.<br />

1. Fault in the removal<br />

mechanism – lock does not<br />

jump outward when circuit<br />

breaker reaches TEST and/or<br />

INSERTED positions.<br />

2. Fault in the removal<br />

mechanism – removal rod<br />

continues free for movement<br />

even after the lock jumps<br />

outward.<br />

3. Fault in removal<br />

mechanism – position<br />

indicator does not work.<br />

1. Poor contact in internal<br />

connections.<br />

2. Parts of the block of<br />

auxiliary contacts damaged.<br />

Maintain the off button<br />

pressed to release the<br />

internal lock and insert the<br />

removal rod.<br />

Turn lightly the removal<br />

rod in the clockwise and<br />

counterclockwise direction<br />

and press the position lock<br />

inward (UNLOCK position).<br />

-<br />

-<br />

-<br />

-<br />

technical<br />

assistance.<br />

Contact WEG<br />

technical<br />

assistance.<br />

Contact WEG<br />

technical<br />

assistance.<br />

.<br />

- Contact WEG<br />

technical<br />

-<br />

assistance.<br />

<strong>ABW</strong> | 73