open <strong>Circuit</strong> <strong>Breaker</strong><br />

Accessories<br />

Items<br />

Closing coils<br />

Opening coils<br />

Auxiliary contacts<br />

Motorized<br />

activation<br />

Auxiliary position<br />

contacts<br />

Subvoltage coil<br />

Method of<br />

Inspection<br />

Electric On<br />

control.<br />

Electric Off<br />

control.<br />

Verification of<br />

continuity.<br />

Verification<br />

of automatic<br />

charging of the<br />

springs.<br />

Verification of<br />

switching.<br />

Verification of<br />

activation of<br />

circuit breaker<br />

Criteria<br />

The circuit breaker must<br />

turn on after coil supply.<br />

The circuit breaker must<br />

turn off after coil supply.<br />

Verify switching of contacts<br />

after operation of the circuit<br />

breaker.<br />

Motorized activation must<br />

automatically charge the<br />

springs of the mechanism<br />

of operation of the circuit<br />

breaker.<br />

Contacts switch according<br />

to position of the circuit<br />

breaker within the removal<br />

carriage.<br />

5.4 InSpeCtIon AFter oCCurrenCe oF trIppIng<br />

70 | <strong>ABW</strong> English<br />

recommended<br />

procedures<br />

Replacement of closing<br />

coil.<br />

Replacement of opening<br />

coil.<br />

Replacement of block of<br />

auxiliary contacts.<br />

Replacement of the<br />

motorized activation.<br />

Replacement of the block<br />

of contacts.<br />

The circuit breaker turns off<br />

Replacement of the coil and<br />

when the subvoltage coil<br />

subvoltage module.<br />

supply (module) is removed.<br />

After opening of the circuit breaker through activation of the protection unit, a detailed<br />

inspection must be made, as described before, for checking its operation.<br />

In addition, the temperature rise of the circuit breaker must be accompanied to check<br />

it operating conditions. In the case of elevated overheating, the circuit breaker must be<br />

replaced.