open <strong>Circuit</strong> <strong>Breaker</strong><br />
Accessories<br />
Items<br />
Closing coils<br />
Opening coils<br />
Auxiliary contacts<br />
Motorized<br />
activation<br />
Auxiliary position<br />
contacts<br />
Subvoltage coil<br />
Method of<br />
Inspection<br />
Electric On<br />
control.<br />
Electric Off<br />
control.<br />
Verification of<br />
continuity.<br />
Verification<br />
of automatic<br />
charging of the<br />
springs.<br />
Verification of<br />
switching.<br />
Verification of<br />
activation of<br />
circuit breaker<br />
Criteria<br />
The circuit breaker must<br />
turn on after coil supply.<br />
The circuit breaker must<br />
turn off after coil supply.<br />
Verify switching of contacts<br />
after operation of the circuit<br />
breaker.<br />
Motorized activation must<br />
automatically charge the<br />
springs of the mechanism<br />
of operation of the circuit<br />
breaker.<br />
Contacts switch according<br />
to position of the circuit<br />
breaker within the removal<br />
carriage.<br />
5.4 InSpeCtIon AFter oCCurrenCe oF trIppIng<br />
70 | <strong>ABW</strong> English<br />
recommended<br />
procedures<br />
Replacement of closing<br />
coil.<br />
Replacement of opening<br />
coil.<br />
Replacement of block of<br />
auxiliary contacts.<br />
Replacement of the<br />
motorized activation.<br />
Replacement of the block<br />
of contacts.<br />
The circuit breaker turns off<br />
Replacement of the coil and<br />
when the subvoltage coil<br />
subvoltage module.<br />
supply (module) is removed.<br />
After opening of the circuit breaker through activation of the protection unit, a detailed<br />
inspection must be made, as described before, for checking its operation.<br />
In addition, the temperature rise of the circuit breaker must be accompanied to check<br />
it operating conditions. In the case of elevated overheating, the circuit breaker must be<br />
replaced.