29.11.2012 Views

Air Circuit Breaker Interruptor Abierto Disjuntor Aberto ABW - Weg

Air Circuit Breaker Interruptor Abierto Disjuntor Aberto ABW - Weg

Air Circuit Breaker Interruptor Abierto Disjuntor Aberto ABW - Weg

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

English<br />

open <strong>Circuit</strong> <strong>Breaker</strong><br />

AttentIon!<br />

reception<br />

Perform visual inspection immediately after reception of the circuit<br />

breaker and even before removing it from the pallet. If there is any<br />

evidence of damage or imperfections caused by transport, directly<br />

inform the carrier and WEG.<br />

transport<br />

Maintain the circuit breaker fastened to the pallet and transport the<br />

assembly with a cart or fork lift.<br />

Observe the following additional recommendations:<br />

Always maintain the pallet in a horizontal position;<br />

Make sure that the load is balanced on the forks of the forklift;<br />

Bind the pallet to the forks so that it does not move or fall over during<br />

transport;<br />

Transport the assembly at low speed, without abrupt movement, avoiding<br />

collisions with other structures, equipment or persons;<br />

Lift the assembly only to the extent necessary to cross over obstacles<br />

on the floor, and never above persons.<br />

Handling / Movement<br />

Removable hooks are provided with each circuit breaker so that it may<br />

be removed from the pallet or removal cart suspended by a winch. This<br />

is the only method recommended for movement of the circuit breaker.<br />

Be careful not to damage the equipment if other methods are used.<br />

Greater details may be conferred on page 20.<br />

Other important recommendations:<br />

Do not pass ropes or cables through the suspension grommets. Always<br />

use locking safety hooks;<br />

Suspension cables must not be less than 45º from horizontal.<br />

Storage<br />

If there is the need to store the circuit breaker before its installation, keep<br />

it in its original packaging, in a clean, dry, ventilated and warm place to<br />

avoid condensation. As with any other electrical equipment, protect it<br />

from dust and humidity. Do not store the circuit breaker in an uncovered<br />

place or exposed to adverse weather conditions.<br />

AttentIon!<br />

Make sure to tighten the bolts of the terminals in accordance with the torques<br />

recommended in this manual. Checking the bolts and tightening them<br />

must be performed periodically, always with all the circuits de-energized<br />

and grounded.<br />

Bolt tightening torque (nm)<br />

Power terminals M12 60<br />

Control terminals M3,5 1,0...1,2<br />

<strong>ABW</strong> | 7

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!