Arch extinguishing Chambers<br />

Items<br />

Method of<br />

Inspection<br />

Dust and debris Visual inspection.<br />

General state of<br />

chamber<br />

Fastening of<br />

chamber<br />

operation Mechanism<br />

Items<br />

Charging of<br />

springs<br />

Turning on and<br />

off<br />

protection unit<br />

Items<br />

External<br />

appearance<br />

Visual inspection.<br />

Verification of<br />

tightening torque.<br />

Method of<br />

Inspection<br />

Operation of<br />

manual charging.<br />

Operation of<br />

turning on and<br />

off by the front<br />

buttons.<br />

Activation Trip test.<br />

Method of<br />

Inspection<br />

Visual inspection.<br />

English<br />

Criteria<br />

There must not be dust or<br />

debris in the inside of the<br />

chamber.<br />

Chambers must be intact,<br />

without cracks or damage.<br />

Fastening bolts must be<br />

tightened with a torque of<br />

9~11 Nm.<br />

Criteria<br />

Verify if the springs can be<br />

charged naturally.<br />

The circuit breaker must<br />

turn on and off normally.<br />

Criteria<br />

Unit must be intact,<br />

without cracks or damage,<br />

including selectors.<br />

The unit must turn on and<br />

off the circuit breaker.<br />

open <strong>Circuit</strong> <strong>Breaker</strong><br />

recommended<br />

procedures<br />

Remove dust and debris<br />

with vacuum and dry cloth.<br />

Replacement of chamber in<br />

case of abnormalities.<br />

Retighten with<br />

recommended torque.<br />

recommended<br />

procedures<br />

Replacement of the circuit<br />

breaker in the ase of<br />

abnormalities.<br />

Replacement of the circuit<br />

breaker in the case of<br />

abnormalities.<br />

recommended<br />

procedures<br />

Replacement of<br />

protection unit in case of<br />

abnormalities.<br />

Replacement of circuit<br />

breaker in case of<br />

abnormalities.<br />

<strong>ABW</strong> | 69

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!