Arch extinguishing Chambers<br />
Items<br />
Method of<br />
Inspection<br />
Dust and debris Visual inspection.<br />
General state of<br />
chamber<br />
Fastening of<br />
chamber<br />
operation Mechanism<br />
Items<br />
Charging of<br />
springs<br />
Turning on and<br />
off<br />
protection unit<br />
Items<br />
External<br />
appearance<br />
Visual inspection.<br />
Verification of<br />
tightening torque.<br />
Method of<br />
Inspection<br />
Operation of<br />
manual charging.<br />
Operation of<br />
turning on and<br />
off by the front<br />
buttons.<br />
Activation Trip test.<br />
Method of<br />
Inspection<br />
Visual inspection.<br />
English<br />
Criteria<br />
There must not be dust or<br />
debris in the inside of the<br />
chamber.<br />
Chambers must be intact,<br />
without cracks or damage.<br />
Fastening bolts must be<br />
tightened with a torque of<br />
9~11 Nm.<br />
Criteria<br />
Verify if the springs can be<br />
charged naturally.<br />
The circuit breaker must<br />
turn on and off normally.<br />
Criteria<br />
Unit must be intact,<br />
without cracks or damage,<br />
including selectors.<br />
The unit must turn on and<br />
off the circuit breaker.<br />
open <strong>Circuit</strong> <strong>Breaker</strong><br />
recommended<br />
procedures<br />
Remove dust and debris<br />
with vacuum and dry cloth.<br />
Replacement of chamber in<br />
case of abnormalities.<br />
Retighten with<br />
recommended torque.<br />
recommended<br />
procedures<br />
Replacement of the circuit<br />
breaker in the ase of<br />
abnormalities.<br />
Replacement of the circuit<br />
breaker in the case of<br />
abnormalities.<br />
recommended<br />
procedures<br />
Replacement of<br />
protection unit in case of<br />
abnormalities.<br />
Replacement of circuit<br />
breaker in case of<br />
abnormalities.<br />
<strong>ABW</strong> | 69