Air Circuit Breaker Interruptor Abierto Disjuntor Aberto ABW - Weg
Air Circuit Breaker Interruptor Abierto Disjuntor Aberto ABW - Weg
Air Circuit Breaker Interruptor Abierto Disjuntor Aberto ABW - Weg
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
open <strong>Circuit</strong> <strong>Breaker</strong><br />
5.3 perIoDIC InSpeCtIon<br />
Monthly periodic inspections are recommended to assure the useful life of the circuit breaker.<br />
Below are items to be inspected and recommended procedures.<br />
external Appearance<br />
Items<br />
Method of<br />
Inspection<br />
Dust and debris Visual inspection<br />
Power<br />
connections<br />
Flooding or<br />
immersion in<br />
water<br />
Control<br />
connections<br />
General state of<br />
cirucuit breaker<br />
power Contacts<br />
Items<br />
Verification of<br />
tightening torque<br />
Visual inspection<br />
Verification of<br />
tightening torque.<br />
Visual inspection<br />
Method of<br />
Inspection<br />
Power contacts Visual inspection.<br />
Power contacts Visual inspection.<br />
Claws of the<br />
removal carriage<br />
Insulation<br />
resistance<br />
Visual inspection.<br />
Criteria<br />
There must not be dust or<br />
debris deposited on the<br />
circuit breaker.<br />
Screws must be tightened<br />
with torque of 60 Nm.<br />
The circuit breaker must<br />
not be used after the<br />
occurrence of flooding or<br />
immersion.<br />
Bolts must be tightened<br />
with torque of 1.0...1.2 Nm.<br />
There must not be<br />
cracks, damage and/or<br />
deformations on the front<br />
lid and base of the circuit<br />
breaker.<br />
68 | <strong>ABW</strong> English<br />
Criteria<br />
There must not be<br />
discoloring of the contacts.<br />
There must not be dust or<br />
debris on the contacts.<br />
See page 67. See page 67.<br />
There must not be<br />
discoloring of the claws or<br />
deformations in the spring.<br />
recommended<br />
procedures<br />
Removal of dust and debris<br />
with vacuum and dry cloth.<br />
Retighten with 60 Nm<br />
torque.<br />
Replacement of circuit<br />
breaker.<br />
Retighten with<br />
recommended torque.<br />
Replacement of the lid or, in<br />
the case of damage at the<br />
base, replacement of the<br />
circuit breaker.<br />
recommended<br />
procedures<br />
Replacement of the circuit<br />
breaker in the case of<br />
discoloring.<br />
Cleaning of contacts.<br />
Replacement of removal<br />
carriage.<br />
Replacement of circuit<br />
breaker in the case of low<br />
insulation resistance.