Items Criteria<br />
Cable and/or bar connection to the<br />
power terminals.<br />
Cleaning of the panel<br />
General state of the circuit breaker<br />
Items preceeding installation<br />
English<br />
open <strong>Circuit</strong> <strong>Breaker</strong><br />
Tighten the M12 bolts in accordance with recommended<br />
torque: 60 Nm.<br />
Remove any foreign materials or remnants from the<br />
installation (bolts, nuts, tools, cable remnants, etc.) of<br />
the panel, principally around the circuit breaker and the<br />
connection terminals.<br />
Check if there are cracks or other damage in the front lid<br />
and base of the circuit breaker.<br />
The circuit breaker must not be turned on after flooding<br />
or if there is condensation on it.<br />
Insulation resistance test Must meet the requirements presented below.<br />
Applied voltage test Must meet the requirements presented below.<br />
Criteria for Insulation resistance test and Applied Voltage test<br />
test points<br />
Insulation<br />
resistance test<br />
Applied<br />
Voltage test<br />
<strong>Circuit</strong> <strong>Breaker</strong> On Off On Off<br />
Between power terminals and ground ■ ■ ■ ■<br />
Between power terminals of different<br />
polarities<br />
■ - ■ -<br />
Between input and output terminals - ■ - ■<br />
Between power terminals and control<br />
terminals<br />
■ ■ ■ ■<br />
Between control terminals and ground ■ ■ ■ ■<br />
test points<br />
Insulation resistance<br />
test<br />
test<br />
Voltage<br />
Criteria of<br />
Approval<br />
Applied Voltage test<br />
test Voltage (1 min)<br />
Between power terminals and ground<br />
Between power terminals of different<br />
polarities<br />
Between input and output terminals<br />
Between power terminals and control<br />
terminals<br />
500 V ≥ 5MΩ<br />
3500 V<br />
Between control terminals and ground 2000 V<br />
AttentIon!<br />
Before performing dielectric tests on the panel, disconnect the terminals<br />
from the subvoltage module.<br />
<strong>ABW</strong> | 67