29.11.2012 Views

Air Circuit Breaker Interruptor Abierto Disjuntor Aberto ABW - Weg

Air Circuit Breaker Interruptor Abierto Disjuntor Aberto ABW - Weg

Air Circuit Breaker Interruptor Abierto Disjuntor Aberto ABW - Weg

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

open <strong>Circuit</strong> <strong>Breaker</strong><br />

5 MAIntenAnCe AnD InSpeCtIon<br />

AttentIon!<br />

The frequency and extent of maintenance and inspection depends on<br />

operating conditions and the environment of installation of the circuit breaker.<br />

Attentively read the recommendations contained in this section before<br />

energizing the circuit breaker.<br />

5.1 prelIMInAry orIentAtIonS<br />

The circuit breakers must be inspected for a part to be detected at the beginning of<br />

deterioration so that performance characteristics are maintained and so that accidents are<br />

prevented that could occur due to the circuit breaker arriving at the end of its useful life.<br />

Frequency of inspection<br />

Application Installation environment Specific examples<br />

General<br />

cases<br />

Special<br />

applications<br />

Environments where the air<br />

is always clean and dry.<br />

Environments with little<br />

dust, free of corrosive<br />

gases.<br />

Salty environment, high<br />

temperatures and presence<br />

of corrosive gases.<br />

Environments with high<br />

concentration of corrosive<br />

gases and/or soot.<br />

5.2 InItIAl InSpeCtIon<br />

66 | <strong>ABW</strong> English<br />

Frequency of<br />

Inspection<br />

Electrical rooms with air<br />

conditioning and anti-dust filters.<br />

Once every 2<br />

years.<br />

Non-climate controlled rooms.<br />

Thermal plants (generation),<br />

water/sewage treatment stations,<br />

metallurgical, paper and cellulose<br />

industry, etc.<br />

Once a year.<br />

Chemical, mining industries, etc. Every 6 months.<br />

previous Inspection before turning on the <strong>Circuit</strong> <strong>Breaker</strong><br />

Below are items to be inspected at the time of installation of the circuit breaker, before<br />

turning it on.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!