open <strong>Circuit</strong> <strong>Breaker</strong><br />

Signaling of Fault through the LEDs:<br />

leD Meaning reset<br />

PICK UP<br />

Lights up when the protection unit begins the trip timing. After<br />

tripping, the LED turns off. For reset of<br />

Lights up when there is tripping through overload (L function), LED, press the<br />

FAULT timed short circuit (S function), instantaneous short circuit (I<br />

function) or lack of ground (G function).<br />

RESET key.<br />

Signaling of Fault through Alarm Contacts:<br />

type of Fault Switch of Contacts reset<br />

Pre-alarm P (T0, T5)<br />

Overload (L function) L,S (T0, T2-); AL1 (AL1+, AL1-); AL2 (AL2+, AL2-)<br />

Timed short circuit (S<br />

function)<br />

Instantaneous short circuit<br />

(I function)<br />

44 | <strong>ABW</strong> English<br />

L,S (T0, T2-); AL1 (AL1+, AL1-); AL2 (AL2+, AL2-)<br />

I (T0, T3); AL1 (AL1+, AL1-); AL2 (AL2+, AL2-)<br />

Lack of ground (G function) G (T0, T4); AL1 (AL1+, AL1-); AL2 (AL2+, AL2-)<br />

navigation Menus<br />

For access to navigation menus, press the ENT key from the start screen.<br />

R: * * * * S: * * * *<br />

T: * * * * N: * * * *<br />

TOP]� 1. CONFIG<br />

+ - 2. SETTING<br />

On the general TOP menu, there is access to the options:<br />

top Menu Function<br />

1. CONFIG (Not available in this model of protection unit).<br />

2. SETTING Setting parameters<br />

3. FAULT Record of the last 10 faults which have occurred<br />

4. CALIBRATE (For factory use – do not change settings)<br />

5. SYSTEM (For factory use – do not change settings)<br />

6. DIAGNOSIS Self-diagnosis of protection unit<br />

7. TEST Test functions of the protection unit<br />

8. TIME SET Setting of date/time<br />

9. Fact Set (For factory use – do not change settings)<br />

ENT<br />

For reset of the<br />

alarm contacts,<br />

press the<br />

RESET key.