Set] Iinst: 25.6k<br />

16 (4-16, OFF)<br />

SET] � 9. Iinst<br />

+ - 1. In<br />

MODE<br />

▼<br />

4 gnD trIp<br />

This function is not available on this model of protection unit.<br />

5 FAult<br />

USR] 4. GND TRIP<br />

+ - � 5. FAULT<br />

ENT<br />

�FLT(1) R<br />

Type : L_INV<br />

▼<br />

FLT(1) R<br />

�Type : L_INV<br />

▼<br />

Type : L_INV<br />

�R: 2.42k S: ****<br />

▼<br />

R: 2.42k S: ****<br />

�T: **** N: ****<br />

▼<br />

T: **** N: ****<br />

�Duty= 14s 545ms<br />

▼<br />

English<br />

open <strong>Circuit</strong> <strong>Breaker</strong><br />

Confirmation of the value chosen on the selector<br />

Iinst (x In).<br />

Iinst = (4 / 6 / 8 / 10 / 12 / 16 / OFF) x In<br />

Record 1 – Phase of occurrence: R.<br />

Type of fault: L_INV (overload – L function).<br />

Fault current: 2420A.<br />

Activation time: 14s 545ms.<br />