29.11.2012 Views

Air Circuit Breaker Interruptor Abierto Disjuntor Aberto ABW - Weg

Air Circuit Breaker Interruptor Abierto Disjuntor Aberto ABW - Weg

Air Circuit Breaker Interruptor Abierto Disjuntor Aberto ABW - Weg

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

On the general menu TOP, there is access to the options: 1.USR and 2.FACT.<br />

Select the option1.USR for access to the user menu:<br />

TOP] � 1. USR<br />

+ - 2. FACT<br />

On the user menu, the following options are available:<br />

Menu uSr Function<br />

1. DIAGNOSIS Self-diagnosis of the protection unit<br />

2. FREQUENCY Confirmation of frequency<br />

3. SETTING Confirmation of set parameters on the front selectors<br />

4. GND TRIP (Not available in this model of protection unit.)<br />

5. FAULT Record of the last 10 faults which occurred<br />

6. TEST Test functions of the protection unit<br />

1 DIAgnoSIS<br />

USR] � 1. DIAGNOSIS<br />

+ - 2. FREQUENCY<br />

ENT<br />

DIA] � 1. COIL: OK<br />

+ - 2. EEP: OK<br />

DIA] 1. COIL: OK<br />

+ - � 2. EEP: OK<br />

2 FreQuenCy<br />

▼<br />

ENT<br />

English<br />

open <strong>Circuit</strong> <strong>Breaker</strong><br />

Verification of the state of connection with the trip<br />

coil: OK (normal) or Fail (fault).<br />

Verification of EEPROM memory.<br />

HAZArD!<br />

If on the DIAGNOSIS menu the display presents the message 1. CoIl:<br />

Fail, contact WEG.<br />

USR] 1. DIAGNOSIS<br />

+ - � 2. FREQUENCY<br />

ENT<br />

FREQ] Freq: 60Hz<br />

(50/60Hz)<br />

Confirmation of frequency.<br />

<strong>ABW</strong> | 33