open <strong>Circuit</strong> <strong>Breaker</strong><br />

electrical operation<br />

The operation of the circuit breaker by electrical command is performed by means of<br />

motorized actvation and by the closing and opening coils, accessories installed internally<br />

in the circuit breaker.<br />

Motorized activation loads the springs of the operating mechanism automatically whenever<br />

the circuit breaker is turned off, an operation that ends after approximately 5 sec. when a<br />

internal auxiliary contact identifies that the springs are completely charged. Power supply<br />

of the motor is made through the M+ and M- terminals (see connection diagram on pages<br />

40 or 54).<br />

There is also an auxiliary contact for indication of charged springs. tS+ and tS- terminals.<br />

To turn on the circuit breaker, with the springs being charged, a pulse of voltage is applied<br />

in the range of 110...220Vac/dc to the terminals of the closing coil: CC+ and CC-.<br />

To turn off the circuit breaker, apply a pulse of voltage in the range of 110...220Vac/dc to<br />

the terminals of the opening coil: S+ and S-.<br />

Both coils operate with a pulse of voltage of only 100ms, not being necessary to keep<br />

them continually energized.<br />

3 proteCtIon unItS<br />

3.1 <strong>ABW</strong>-oCr116<br />

LEDs FOR<br />

SIGNALING<br />

FAULTS<br />

NAVIGATION<br />

KEYS<br />

30 | <strong>ABW</strong> English<br />

LCD DISPLAY<br />

LED RUN<br />

RESET KEY<br />

SETTING<br />

SELECTORS