open <strong>Circuit</strong> <strong>Breaker</strong><br />

AttentIon!<br />

Before pulling the circuit breaker, check if the removal carriage is fastened<br />

to the panel. If not, hold it so that it does not fall over with the weight of the<br />

circuit breaker.<br />

In the REMOVED position, the power and control circuits are disconnected.<br />

removal – <strong>Circuit</strong> <strong>Breaker</strong>s <strong>ABW</strong>40...50<br />

Press the off button to turn off the circuit breaker.<br />

Locate and loosen the side fasteners, using the removal rod itself, and pull them upward,<br />

releasing the circuit breaker.<br />

LOOSE<br />

FASTENER<br />

Then follow procedures E2), E3) and E4), described above to bring the circuit breaker to<br />

the TEST position.<br />

Repeat these same procedures to bring it to the REMOVED position.<br />