open <strong>Circuit</strong> <strong>Breaker</strong><br />

AttentIon!<br />

If there is difficulty in pressing the lock inward, make light movements with<br />

the removal rod in clockwise and counterclockwise directions.<br />

E4) Then, with the lock in the UNLOCK position, turn the removal rod a few turns in the<br />

counterclockwise direction until the circuit breaker arrives at the TEST position. At this<br />

moment the lock jumps outward again (LOCK).<br />

AttentIon!<br />

Never turn the removal rod withthe lock in the LOCK position.<br />

The TEST position can be confirmed by the position indicator.<br />

If the lock jumps outward immediately in the first turns of the rod without the circuit breaker<br />

having arrived at the TEST position, press the lock inward and continue the operation.<br />

In the TEST position, the power circuits are disconnected and the control circuits are<br />

connected.<br />

E5) To bring the circuit breaker to the REMOVED (DISCONNECTED) position, repeat<br />

procedures E2), E3) and E4).<br />

If desired, the circuit breaker may be pulled by the tracks and totally removed from the<br />

removal carriage.<br />