1.4 teCHnICAl InForMAtIon<br />

English<br />

open <strong>Circuit</strong> <strong>Breaker</strong><br />

<strong>ABW</strong>16 <strong>ABW</strong>20 <strong>ABW</strong>25 <strong>ABW</strong>32 <strong>ABW</strong>40 <strong>ABW</strong>50<br />

Maximum nominal current<br />

(40°C) - In max. (A)<br />

1600 2000 2500 3200 4000 5000<br />

Nominal operation voltage - Ue<br />

(V)<br />

690<br />

Nominal insulation voltage - Ui<br />

(V)<br />

1000<br />

Inpulse voltage - Uimp (kV) 8<br />

Frequency (Hz) 50 / 60<br />

Number of poles 3<br />

Versions Fixed – Removable<br />

Protection units Electronic<br />

Short circuit 220/380/415V 65 85 100<br />

interruption<br />

capacity - Icu<br />

(kA)<br />

440V<br />

500V<br />

600V<br />

690V<br />

65<br />

65<br />

50<br />

50<br />

85<br />

85<br />

65<br />

50<br />

100<br />

100<br />

85<br />

50<br />

Short circuit 220/380/415V 65 85 100<br />

interrution<br />

capacity - Ics<br />

(kA)<br />

440V<br />

500V<br />

600V<br />

690V<br />

65<br />

65<br />

50<br />

50<br />

85<br />

85<br />

65<br />

50<br />

100<br />

100<br />

85<br />

50<br />

Supportability 1s 65 65 85<br />

to short circuit - 2s 60 60 65<br />

Icw (kA)<br />

3s 50 60 65<br />

Capacity of 220/380/415V 143 187 220<br />

establishment 440V 143 187 220<br />

of short circuit 500V 143 187 220<br />

(peak value) - 600V 105 143 187<br />

Icm (kA)<br />

690V 105 105 105<br />

Category of use B<br />

Time of<br />

Opening ≤ 40<br />

operation (ms) Closing ≤ 80<br />

Mechanical life (no. of operations) 12000 10000<br />

Electrical life (no. of operations) 3000<br />

Altitude (m) ≤ 2000 (1)<br />

Ambient Operation -5...40°C<br />

temperature<br />

(2)<br />

Storage -20...60°C<br />

Thermal dissipation at<br />

nominal current (W)<br />

52 160 250 410 960 1500<br />

Weight (kg)<br />

Removable (3) Fixed<br />

64<br />

41<br />

92<br />

60<br />

93<br />

61<br />

95<br />

63<br />

240<br />

115<br />

240<br />

115<br />

Power<br />

Removable Horizontal<br />

terminals<br />

(4) Vertical<br />

Fixed Horizontal (4) Horizontal (4)<br />

Dimensions - Removable 339 x 435 x 379 474x435x379 961x459x379<br />

LxHxD (mm)<br />

Notes:<br />

Fixed 315 x 410 x 295 450x410x295 840x410x295<br />

(1) For installation above 2000m, apply correction factors for nominal voltage and current, in accordance with the<br />

table on page 9.<br />

(2) For ambient temperature above 40°C, check maximum values of the nominal currents on the table on page 9.<br />

(3) Includes removal carriage.<br />

(4) Vertical terminals available as accessories. See page 62.<br />