Disyuntor <strong>Abierto</strong><br />

Set] Ip: 4.00k<br />

1.0 (0.7-1.0)<br />

ENT<br />

SET] 7. GTD<br />

+ - � 8. Ip (*Ic)<br />

118 | <strong>ABW</strong> Español<br />

▼<br />

SET] 8. Ip (*Ic)<br />

+ - � 9. Iinst<br />

ENT<br />

Set] Inst: 64.0k<br />

16 (2-16, no)<br />

ENT<br />

SET] 8. Ip (*Ic)<br />

+ - � 9. Iinst<br />

▼<br />

SET] 9. Iinst<br />

+ - � 10. Update<br />

ENT<br />

Update Setting<br />

<br />

ENT<br />

SET] 9. Iinst<br />

+ - � 10. Update<br />

Ajuste de la corriente Ip (x In). Utilizar la tecla<br />

� y �.<br />

Ip = (0,7 / 0,8 / 0,9 / 1,0) x In<br />

Ajuste de la corriente Iinst (x In). Utilizar la tecla<br />

� y �.<br />

Iinst = (2 / 3 / 4 ... 14 / 15 / 16 / no) x In para<br />

<strong>ABW</strong>40<br />

Iinst = (2 / 3 / 4 ... 10 / 11 / 12 / no) x In para<br />

<strong>ABW</strong>50<br />