Troubleshooting AirCon Service Center 11 Troubleshooting Problem Cause Remedy The display shows “Warning! Internal vessel overpressure!” The display shows “Warning! Internal vessel full!” The display shows “Warning! Pressure inside the A/C system. Recovery start!” The display shows “Warning! Pressure inside the A/C system!” The display shows “Not enough vacuum! Carry on?” The display shows “A/C system leakage! Carry on?” The display shows “Drained oil glass emptying!” The display shows “Warning! Not enough vacuum for injection!” The display shows “Quantity too large. Fill internal vessel!” Normal message that appears during the recycling process. The internal refrigerant container is too full to hold the quantity to be extracted. Normal message that appears at the start of the vacuum process. There is still pressure present in the air conditioning system. Message during the vacuum process. There is pressure in the air conditioning system. Message that appears during the vacuum process if the pressure in the air conditioning system after 8 minutes is still more than 50 mbar. Message at the end of the vacuum process. The air conditioning system shows a vacuum loss of more than 120 mbar during the checking time. This message appears during the extraction or recycling process if there is more than 150 ml of used oil in the container. Message that appears during the filling phase if the vacuum in the air conditioning system is insufficient to end the process. Message that appears during the process input if there is not enough refrigerant in the internal container to complete the process. To continue, press ENTER for three seconds. If this message appears repeatedly, notify customer services. Drain the internal refrigerant container in the proper manner. No action is required. The process continues automatically. No action is required. The process continues automatically. Check the air conditioning system or the connections between it and the AirConServiceCenter for leaks. Check the air conditioning system or the connections between it and the AirConServiceCenter for leaks. Dispose of the content of the used oil container in an environmentally responsible manner. Check the air conditioning system or the connections between it and the AirConServiceCenter for leaks. Fill the refrigerant container. 106 EN
AirCon Service Center Troubleshooting Problem Cause Remedy The display shows “Not enough UV. Add!” The display shows “Not enough oil. Add!” The display shows “Max. filling time exceeded! Carry on?” The display shows “External tank empty or closed valve. Check!” The display shows “Change the equipment drier filter! Carry on?” The display shows “Change the vacuum pump oil! Carry on?” The display shows “Printer not in line! Carry on?” The display shows “Error 01” The display shows “Error 02” The display shows “Error 09” This message appears during the filling process if there is not enough UV additive in the container to finish the process. Message that appears during the filling process if there is not enough fresh oil in the container to finish the process. Message that appears during the filling process if the set amount of refrigerant cannot be filled. Message that appears at the start or during the filling of the internal refrigerant container if the set refrigerant quantity cannot be attained. This message appears when you switch on the AirConServiceCenter. This message appears when you switch on the AirConServiceCenter. Message indicates a printer fault. Refrigerant was added before draining was completed. The air conditioning system is leaking. There is still refrigerant in the air conditioning system. Low pressure connector not connected to the flush container during flushing. Fill the UV additive container. Top up the fresh oil container with a suitable oil type. Check that AirConServiceCenter connections are not blocked. Check if the external refrigerant container still contains enough refrigerant or if the valves of the external refrigerant container are open. Change the internal filter as soon as possible (see Page 92). To skip this, press ENTER for 3 seconds. Change the vacuum pump oil as soon as possible (see Page 96). To skip this, press ENTER for 3 seconds. Check if there is paper in the printer. Check if the printer is switched on (yellow LED must light up constantly). Check that the cover is closed properly. Repeat the draining procedure; do not interrupt it this time. Fix the leak. Connect low pressure hose to the flush box and open valve. EN 107
- Page 56 and 57: Contents AirCon Service Center 1 Ab
- Page 58 and 59: About this operating manual AirCon
- Page 60 and 61: Safety AirCon Service Center Each t
- Page 62 and 63: Optional extras AirCon Service Cent
- Page 64 and 65: Overview of the AirConServiceCenter
- Page 66 and 67: Initial start-up AirCon Service Cen
- Page 68 and 69: Initial start-up AirCon Service Cen
- Page 70 and 71: Initial start-up AirCon Service Cen
- Page 72 and 73: Initial start-up AirCon Service Cen
- Page 74 and 75: Operation AirCon Service Center 8 O
- Page 76 and 77: Operation AirCon Service Center 8.2
- Page 78 and 79: Operation AirCon Service Center 8.2
- Page 80 and 81: Operation AirCon Service Center 8.
- Page 82 and 83: Operation AirCon Service Center 8.5
- Page 84 and 85: Operation AirCon Service Center 8.6
- Page 86 and 87: Operation AirCon Service Center 8.6
- Page 88 and 89: Operation AirCon Service Center 3.
- Page 90 and 91: Service tasks AirCon Service Center
- Page 92 and 93: Service tasks AirCon Service Center
- Page 94 and 95: Service tasks AirCon Service Center
- Page 96 and 97: Service tasks AirCon Service Center
- Page 98 and 99: Service tasks AirCon Service Center
- Page 100 and 101: Service tasks AirCon Service Center
- Page 102 and 103: Service tasks AirCon Service Center
- Page 104 and 105: Service tasks AirCon Service Center
- Page 108 and 109: Technical data AirCon Service Cente
- Page 110 and 111: Acerca de estas instrucciones de us
- Page 112 and 113: Seguridad AirCon Service Center 2 S
- Page 114 and 115: Volumen de entrega AirCon Service C
- Page 116 and 117: Vista general del AirConServiceCent
- Page 118 and 119: Primera puesta en funcionamiento Ai
- Page 120 and 121: Primera puesta en funcionamiento Ai
- Page 122 and 123: Primera puesta en funcionamiento Ai
- Page 124 and 125: Primera puesta en funcionamiento Ai
- Page 126 and 127: Primera puesta en funcionamiento Ai
- Page 128 and 129: Funcionamiento AirCon Service Cente
- Page 130 and 131: Funcionamiento AirCon Service Cente
- Page 132 and 133: Funcionamiento AirCon Service Cente
- Page 134 and 135: Funcionamiento AirCon Service Cente
- Page 136 and 137: Funcionamiento AirCon Service Cente
- Page 138 and 139: Funcionamiento AirCon Service Cente
- Page 140 and 141: Funcionamiento AirCon Service Cente
- Page 142 and 143: Funcionamiento AirCon Service Cente
- Page 144 and 145: Trabajos de mantenimiento AirCon Se
- Page 146 and 147: Trabajos de mantenimiento AirCon Se
- Page 148 and 149: Trabajos de mantenimiento AirCon Se
- Page 150 and 151: Trabajos de mantenimiento AirCon Se
- Page 152 and 153: Trabajos de mantenimiento AirCon Se
- Page 154 and 155: Trabajos de mantenimiento AirCon Se
Troubleshooting<br />
<strong>AirCon</strong> <strong>Service</strong> Center<br />
11 Troubleshooting<br />
Problem Cause Remedy<br />
The display shows<br />
“Warning!<br />
Internal vessel<br />
overpressure!”<br />
The display shows<br />
“Warning!<br />
Internal vessel full!”<br />
The display shows<br />
“Warning!<br />
Pressure inside the A/C<br />
system.<br />
Recovery start!”<br />
The display shows<br />
“Warning!<br />
Pressure inside the A/C<br />
system!”<br />
The display shows<br />
“Not enough vacuum!<br />
Carry on?”<br />
The display shows<br />
“A/C system leakage!<br />
Carry on?”<br />
The display shows<br />
“Drained oil glass<br />
emptying!”<br />
The display shows<br />
“Warning!<br />
Not enough vacuum for<br />
injection!”<br />
The display shows<br />
“Quantity too large.<br />
Fill internal vessel!”<br />
Normal message that<br />
appears during the recycling<br />
process.<br />
The internal refrigerant<br />
container is too full to hold<br />
the quantity to be extracted.<br />
Normal message that<br />
appears at the start of the<br />
vacuum process. There is<br />
still pressure present in the<br />
air conditioning system.<br />
Message during the vacuum<br />
process. There is pressure in<br />
the air conditioning system.<br />
Message that appears during<br />
the vacuum process if the<br />
pressure in the air<br />
conditioning system after<br />
8 minutes is still more than<br />
50 mbar.<br />
Message at the end of the<br />
vacuum process. The air<br />
conditioning system shows a<br />
vacuum loss of more than<br />
120 mbar during the<br />
checking time.<br />
This message appears<br />
during the extraction or<br />
recycling process if there is<br />
more than 150 ml of used oil<br />
in the container.<br />
Message that appears during<br />
the filling phase if the<br />
vacuum in the air<br />
conditioning system is<br />
insufficient to end the<br />
process.<br />
Message that appears during<br />
the process input if there is<br />
not enough refrigerant in the<br />
internal container to<br />
complete the process.<br />
To continue, press ENTER<br />
for three seconds.<br />
If this message appears<br />
repeatedly, notify customer<br />
services.<br />
Drain the internal refrigerant<br />
container in the proper<br />
manner.<br />
No action is required. The<br />
process continues<br />
automatically.<br />
No action is required. The<br />
process continues<br />
automatically.<br />
Check the air conditioning<br />
system or the connections<br />
between it and the<br />
<strong><strong>AirCon</strong><strong>Service</strong>Center</strong> for<br />
leaks.<br />
Check the air conditioning<br />
system or the connections<br />
between it and the<br />
<strong><strong>AirCon</strong><strong>Service</strong>Center</strong> for<br />
leaks.<br />
Dispose of the content of the<br />
used oil container in an<br />
environmentally responsible<br />
manner.<br />
Check the air conditioning<br />
system or the connections<br />
between it and the<br />
<strong><strong>AirCon</strong><strong>Service</strong>Center</strong> for<br />
leaks.<br />
Fill the refrigerant container.<br />
106<br />
EN