2 Mechanical Installation<br />

2. Route the cables through the cable glands, following the instructions in Cable Glands on page 10.<br />

3. Tighten the cable gland caps.<br />

Cable<br />

EMC Filter<br />

Terminals<br />

grounding<br />

of cable shield<br />

Cable Gland<br />

(Cap)<br />

4. Connect the power supply cable to the EMC Filter. Use only the green colored screws for grounding. Connect motor cable to inverter main<br />

terminals and control circuit to the control terminals.<br />

5. Install option cards if required. For drives CIMR-VCBAHAA-00 and CIMR-VC4A0001HAA-00 to CIMR-VC4A0011HAA-<br />

00 place the bottom cover and terminal cover delivered with the drive before attaching the option card.<br />

2. Sostituite il<br />

coperchio terminali.<br />

3. Installare la<br />

scheda opzionale.<br />

1. Sostituite il coperchio<br />

inferiore.<br />

• Reattaching the Front Cover<br />

NOTICE: Be careful not to pinch or damage the front cover sealing when attaching the front cover. Any damage to the sealing may allow moisture or oil to enter the drive<br />

case and damage components.<br />

NOTICE: Equipment Hazard. Be sure to fastening all screws in accordance with specified tightening torque. If any screws are loose, water and oil may seep into the case<br />

and damage the drive.<br />

1. For drives with digital operator in the front cover insert the LED operator cable back into the correct port on the drive.<br />

2. Place the front cover back onto the drive, and fasten the cover screws applying the following tightening torque values:<br />

<strong>Drive</strong>s CIMR-VCBA and CIMR-VC4A0001 to 0011: 1.5 Nm<br />

<strong>Drive</strong>s CIMR-VC4A0018 to 0038: 2.5 Nm<br />

<br />

Cable Glands<br />

NOTICE: Equipment Hazard. Use only the recommended multiconductor cable and use one cable per cable gland only. Attempting to pass more than one wire through a<br />

cable gland will result in a space between those wires, thus considerably reducing the water-proofing and dust-proofing capabilities of the cable gland, and may<br />

result in damaging the drive.<br />

NOTICE: Make sure that the rubber edging along the outside of the cable gland is properly sealed. Failing to properly seal the outside may allow water or oil into the drive<br />

and damage components.<br />

• Cable Glands Specifications and Model Numbers<br />

<strong>YASKAWA</strong> recommends using SKINTOP cable glands by Lapp Kabel for use with <strong>V1000</strong> Series <strong>IP66</strong> <strong>Type</strong>.<br />

EN 10<br />