9.3.4 Buttons on pump<br />

The operating buttons<br />

to these values:<br />

and on the control panel can be set<br />

• Active<br />

• Not active.<br />

When set to Not active (locked), the buttons do not function.<br />

Set the buttons to Not active if the pump should be controlled via<br />

an external control system.<br />

9.3.5 Pump number<br />

A number between 1 and 64 can be allocated to the pump. In the<br />

case of bus communication, a number must be allocated to each<br />

pump.<br />

9.3.6 Digital input<br />

The digital input of the pump (terminal 1, figs. 4, 8 and 14) can be<br />

set to different functions.<br />

Select one of the following functions:<br />

• Min. (min. curve)<br />

• Max. (max. curve).<br />

The selected function is activated by closing the contact between<br />

terminals 1 and 9 (figs. 4, 8 and 14).<br />

See also section 12.2 Digital input.<br />

Min.:<br />

When the input is activated, the pump is operating according to<br />

the min. curve.<br />

Max.:<br />

When the input is activated, the pump is operating according to<br />

the max. curve.<br />

9.3.7 Motor bearing monitoring (only 11-22 kW)<br />

The motor bearing monitoring function can be set to these values:<br />

• Active<br />

• Not active.<br />

When the function is set to Active, a counter in the controller will<br />

start counting the mileage of the bearings. See section<br />

9.2.7 Lubrication status of motor bearings (only 11-22 kW).<br />

Note<br />

9.3.8 Confirming relubrication/replacement of motor<br />

bearings (only 11-22 kW)<br />

This function can be set to these values:<br />

• Relubricated<br />

• Replaced<br />

• Nothing done.<br />

When the bearing monitoring function is Active, the controller will<br />

give a warning indication when the motor bearings are due to be<br />

relubricated or replaced. See section 9.1.3 Fault indications.<br />

When the motor bearings have been relubricated or replaced,<br />

confirm this action in the above display by pressing "OK".<br />

Note<br />

The counter will continue counting even if the<br />

function is switched to Not active, but a warning<br />

will not be given when it is time for relubrication.<br />

When the function is switched to Active again,<br />

the accumulated mileage will again be used to<br />

calculate the relubrication time.<br />

Relubricated cannot be selected for a period of<br />

time after confirming relubrication.<br />

9.3.9 Standstill heating (only 11-22 kW)<br />

The standstill heating function can be set to these values:<br />

• Active<br />

• Not active.<br />

When the function is set to Active, a DC voltage will be applied to<br />

the motor windings. The applied DC voltage will ensure that<br />

sufficient heat is generated to avoid condensation in the motor.<br />

25