6.3.1 Guide to the selection of control mode based on system type<br />

System type System description Select this control mode<br />

Relatively big pressure<br />

losses in the boiler, chiller<br />

or heat exchanger circuit<br />

and the pipes.<br />

Relatively small pressure<br />

losses in the boiler, chiller<br />

or heat exchanger circuit<br />

and the pipes.<br />

6.4 Factory setting<br />

1. Two-pipe • with a dimensioned pump head higher than 4 metres<br />

heating • very long distribution pipes<br />

systems with<br />

thermostatic<br />

• strongly throttled pipe balancing valves<br />

valves • differential pressure regulators<br />

• big pressure losses in those parts of the system through<br />

which the total quantity of water flows (e.g. boiler, chiller,<br />

heat exchanger and pipes up to the first branching).<br />

2. Primary circuit pumps in systems with big pressure losses in the primary<br />

circuit.<br />

1. Two-pipe • with a dimensioned pump head lower than 2 metres<br />

heating or • dimensioned for natural circulation<br />

cooling<br />

systems with<br />

• with small head losses in those parts of the system<br />

through which the total quantity of water flows<br />

thermostatic<br />

(e.g. boiler, chiller, heat exchanger and pipes up to the<br />

valves<br />

first branching)<br />

• modified to a high differential temperature between flow<br />

pipe and return pipe (e.g. district heating).<br />

2. Floor heating systems with thermostatic valves.<br />

3. One-pipe heating systems with thermostatic valves or pipe balancing<br />

valves.<br />

4. Primary circuit pumps in systems with small pressure losses in the primary<br />

circuit.<br />

<strong>TPE</strong> pumps:<br />

The pumps have been factory-set to proportional pressure.<br />

The head corresponds to 50 % of the maximum pump head (see<br />

data sheet for the pump).<br />

Many systems will operate satisfactorily with the factory setting,<br />

but most systems can be optimized by changing this setting.<br />

In sections 9.1 Menu OPERATION and 9.3 Menu<br />

INSTALLATION, the factory setting is marked with bold-faced<br />

type under each individual display.<br />

Proportional pressure<br />

Constant pressure<br />

<strong>TPE</strong>D pumps:<br />

The pumps have been factory-set to proportional pressure and<br />

the additional operating mode “alternating operation”.<br />

The head corresponds to 50 % of the maximum pump head<br />

(see data sheet for the pump).<br />

Many systems will operate satisfactorily with the factory setting,<br />

but most systems can be optimized by changing this setting.<br />

In sections 9.1 Menu OPERATION and 9.3 Menu<br />

INSTALLATION, the factory setting is marked with bold-faced<br />

type under each individual display.<br />

17