Tabla III<br />

Refuerzos exteriores (presión máx.: 500 Pa)<br />

Dimensión interior<br />

Máxima (mm)<br />

Rigi<strong>de</strong>z <strong>de</strong>l panel<br />

<strong>CLIMAVER</strong> PLUS R, <strong>CLIMAVER</strong> Neto, <strong>CLIMAVER</strong> A2, A2 Neto<br />

y Sistema <strong>CLIMAVER</strong> METAL<br />

Distancia (m)<br />

0,4 0,6<br />

≤ 375 ● ●<br />

376 - 450 ● ●<br />

451 - 600 ● ●<br />

601 - 750 ➡ (0,8) 25<br />

751 - 900 ➡ (0,8) 25<br />

901 - 1.050 ➡ (0,8) 25<br />

1.051 - 1.200 ➡ (0,8) 25<br />

1.201 - 1.500 ➡ (0,8) 30<br />

1.501 - 1.800 ➡ (1,2) 30<br />

1.801 - 2.100 ➡ (1,2) 40<br />

2.101 - 2.400 ➡ (1,2) 50<br />

● El conducto no necesita refuerzos.<br />

■ El conducto no pue<strong>de</strong> tener refuerzos a esa distancia.<br />

➡ El conducto pue<strong>de</strong> tener el refuerzo correspondiente a la distancia superior.<br />

Entre paréntesis figura el espesor <strong>de</strong> la chapa y la altura <strong>de</strong>l refuerzo.<br />