Appendix Piping Connection 1. Form the piping according to its routing. Avoid bending and bending back the same piping point more than three times. (This will result in hardening the pipe.) 2. After deforming the piping, align centers of the union fitting of the indoor unit and the piping, and tighten them firmly with wrenches. 3. Connect pipe to the service valve or ball valve which is located below the outdoor unit. 4. After completing the piping connection, be sure to check if there is gas leakage in indoor and outdoor connection. Vacuum drying After completing the piping connection, execute vacuum drying for the connecting piping and the indoor unit. The vacuum drying must be carried out using the service ports of both the liquid and gas side valves. Capacity(kW) Liquid side piping(mm) Gas side piping(mm) 5.3, 7.0 Ø6.35 Ø9.53 8.8 Ø9.53 Ø9.53 10.5 Ø9.53 Ø9.53 12.3 Ø9.53 Ø19.05 14.1 Ø9.53 Ø19.05 17.6 Ø12.7 Ø19.05 CAUTION Use two wrenches and tighten with regular torque. Ø6.35mm Flare nut fastening torque 1.8kg . m Ø9.52mm 4.0kg . m Ø12.7mm 5.5kg . m Ø15.88mm 6.6kg . m Ø19.05mm 6.6kg . m 54 Outdoor Unit Outdoor unit Liquid side Gas side Blazing connection Indoor unit Flare connection Union
HEAT INSULATION Appendix 1. Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C). Fastening band (accessory) 2. Precautions in high humidity circumstance: This air conditioner has been tested according to the "KS Standard Conditions with Mist" and confirmed that there is not any default. However, if it is operated for a long time in high humid atmosphere (dew point temperature: more than 23°C), water drops are liable to fall. In this case, add heat insulation material according to the following procedure: • Heat insulation material to be prepared... Adiabatic glass wool with thickness 10 to 20mm. Indoor unit Refrigerant piping Thermal insulator (accessory) • Stick glass wool on all air conditioners that are located in ceiling atmosphere. • In addition to the normal heat insulation (thickness: more than 8mm) for refrigerant piping (gas piping: thick piping) and drain piping, add further 10mm to 30mm thickness material. Installation Manual 55 ENGLISH
- Page 3 and 4: Safety Precautions Safety Precautio
- Page 5 and 6: Install the air conditioner accordi
- Page 7 and 8: Do not install the outdoor unit at
- Page 9 and 10: Cautions before the test run Turn o
- Page 11 and 12: Combination with indoor and Outdoor
- Page 13 and 14: Installation Space Individual Insta
- Page 15 and 16: Collective / Continuous installatio
- Page 17 and 18: Installation Location of anchor bol
- Page 19 and 20: Refrigerant piping installation A T
- Page 21 and 22: Refrigerant piping system ◆ Y bra
- Page 23 and 24: ◆ Header Method CRUN458S0 Example
- Page 25 and 26: ◆ Combination of Y branch/header
- Page 27 and 28: ◆ Indoor Unit Connection 50m H A
- Page 29 and 30: Branch pipe Fitting A A Y branch He
- Page 31 and 32: Airtight Test and Evacuation (1) Ai
- Page 33 and 34: Electrical Wiring Areas of Caution
- Page 35 and 36: Transmission and Power Lines 1) Tra
- Page 37 and 38: ◆ Example Connection of Transmiss
- Page 39 and 40: ◆ The Procedure of Automatic Addr
- Page 41 and 42: Group Number Setting for Indoor Uni
- Page 43 and 44: ◆ Position of rotary switch on th
- Page 45 and 46: Test Run Checks Before Test Run 1 2
- Page 47 and 48: Self-Diagnosis Function Error Indic
- Page 49 and 50: Position of the LED01Y in inverter
- Page 51 and 52: Piping Diagram CRUN458S0 4way valve
- Page 53: Preparation of Piping Appendix Main
- Page 57 and 58: 3. Grouped drain piping Appendix 1)
- Page 59 and 60: Indoor unit A B C D E F G H I J K L
- Page 61 and 62: Prior to power on Outdoor unit Indo
- Page 63 and 64: MANUALE D’INSTALLAZIONE MODELLO N
- Page 65 and 66: Precauzioni di sicurezza Precauzion
- Page 67 and 68: Installare il condizionatore d’ar
- Page 69 and 70: Non installare l’unità esterna s
- Page 71 and 72: Avvertenze per l’esecuzione dei t
- Page 73 and 74: Combinazione con le unità interne
- Page 75 and 76: Spazio necessario attorno all’uni
- Page 77 and 78: Installazione multipla e installazi
- Page 79 and 80: Installazione Posizione del bullone
- Page 81 and 82: Installazione della tubatura refrig
- Page 83 and 84: Sistema di tubatura refrigerante
- Page 85 and 86: ◆ Metodo di diramazione del colle
- Page 87 and 88: ◆ Metodo di diramazione del colle
- Page 89 and 90: ◆ Tubo di collegamento unità int
- Page 91 and 92: A Installazione del tubo di diramaz
- Page 93 and 94: Test tenuta d’aria e fuoriuscite
- Page 95 and 96: Lavoro elettrico Avviso TB6 TB6 TB6
- Page 97 and 98: Linee di trasmissione e di alimenta
- Page 99 and 100: ◆ Esempio di collegamento del cav
- Page 101 and 102: ◆ Procedimento di indirizzamento
- Page 103 and 104: Impostazione del numero di gruppo M
HEAT INSULATION<br />
Appendix<br />
1. Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over<br />
120°C).<br />
Fastening band<br />
(accessory)<br />
2. Precautions in high humidity circumstance:<br />
This air conditioner has been tested according to the<br />
"KS Standard Conditions with Mist" and confirmed<br />
that there is not any default. However, if it is operated<br />
for a long time in high humid atmosphere (dew point<br />
temperature: more than 23°C), water drops are liable<br />
to fall. In this case, add heat insulation material<br />
according to the following procedure:<br />
• <strong>Heat</strong> insulation material to be prepared... Adiabatic<br />
glass wool with thickness 10 to 20mm.<br />
Indoor unit<br />
Refrigerant piping<br />
Thermal insulator<br />
(accessory)<br />
• Stick glass wool on all air conditioners that are located in ceiling atmosphere.<br />
• In addition to the normal heat insulation (thickness: more than 8mm) for refrigerant piping (gas piping: thick<br />
piping) and drain piping, add further 10mm to 30mm thickness material.<br />
Installation Manual 55<br />
ENGLISH