System Heat Pump Outdoor Unit - MegaFrio
System Heat Pump Outdoor Unit - MegaFrio System Heat Pump Outdoor Unit - MegaFrio
Appendix CRUN1008T0 High pressure Sensor 4way valve Air TH HOT GAS BYPASS Low pressure Sensor 52 Outdoor Unit Oil separator Oil separator High pressure S/W High pressure S/W LEV Inverter Normal LEV comp. comp. Accumulator LIQUID INJECTION Receiver : Strainer : Solenoid valve : Thermistor : Check valve Dryer : Cooling : Heating
Preparation of Piping Appendix Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure. 1) Cut the pipes and the cable. ■ Use the accessory piping kit or the pipes purchased locally. ■ Measure the distance between the indoor and the outdoor unit. ■ Cut the pipes a little longer than measured distance. ■ Cut the cable 1.5m longer than the pipe length. 2) Burrs removal ■ Completely remove all burrs from the cut cross section of pipe/tube. ■ Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the tubing. 3) Putting nut on ■ Remove flare nuts attached to indoor and outdoor units, then put them on pipe/tube having completed burr removal. (Not possible to put them on after flaring work) 4) Flaring work ■ Carry out flaring work using flaring tool as shown below. Capacity Outside Diameter Gas Liquid Gas "A " Liquid 18k Btu/h 5/8" 1/4" 0.8~1.0 0~0.5 24k Btu/h 5/8" 1/4" 0.8~1.0 0~0.5 30k Btu/h 5/8" 3/8" 0.8~1.0 0.5~0.8 36k Btu/h 5/8" 3/8" 0.8~1.0 0.5~0.8 42k Btu/h 3/4" 3/8" 1.0~1.3 0.5~0.8 48k Btu/h 3/4" 3/8" 1.0~1.3 0.5~0.8 60k Btu/h 3/4" 1/2" 1.0~1.3 0.5~0.8 Firmly hold copper tube in a bar(or die) as indicated dimension in the table above. 5) Check ■ Compare the flared work with figure below. ■ If flare is noted to be defective, cut off the flared section and do flaring work again. Copper tube 90° Slanted Uneven Rough Bar Point down Copper tube Copper pipe Smooth all round Even length all round "A" Pipe Flare nut Bar Clamp handle Inclined Reamer Handle Yoke Cone Red arrow mark Inside is shining without scratches. = Improper flaring = Surface Cracked Uneven damaged thickness Installation Manual 53 ENGLISH
- Page 1 and 2: System Heat Pump Outdoor Unit INSTA
- Page 3 and 4: Safety Precautions Safety Precautio
- Page 5 and 6: Install the air conditioner accordi
- Page 7 and 8: Do not install the outdoor unit at
- Page 9 and 10: Cautions before the test run Turn o
- Page 11 and 12: Combination with indoor and Outdoor
- Page 13 and 14: Installation Space Individual Insta
- Page 15 and 16: Collective / Continuous installatio
- Page 17 and 18: Installation Location of anchor bol
- Page 19 and 20: Refrigerant piping installation A T
- Page 21 and 22: Refrigerant piping system ◆ Y bra
- Page 23 and 24: ◆ Header Method CRUN458S0 Example
- Page 25 and 26: ◆ Combination of Y branch/header
- Page 27 and 28: ◆ Indoor Unit Connection 50m H A
- Page 29 and 30: Branch pipe Fitting A A Y branch He
- Page 31 and 32: Airtight Test and Evacuation (1) Ai
- Page 33 and 34: Electrical Wiring Areas of Caution
- Page 35 and 36: Transmission and Power Lines 1) Tra
- Page 37 and 38: ◆ Example Connection of Transmiss
- Page 39 and 40: ◆ The Procedure of Automatic Addr
- Page 41 and 42: Group Number Setting for Indoor Uni
- Page 43 and 44: ◆ Position of rotary switch on th
- Page 45 and 46: Test Run Checks Before Test Run 1 2
- Page 47 and 48: Self-Diagnosis Function Error Indic
- Page 49 and 50: Position of the LED01Y in inverter
- Page 51: Piping Diagram CRUN458S0 4way valve
- Page 55 and 56: HEAT INSULATION Appendix 1. Use the
- Page 57 and 58: 3. Grouped drain piping Appendix 1)
- Page 59 and 60: Indoor unit A B C D E F G H I J K L
- Page 61 and 62: Prior to power on Outdoor unit Indo
- Page 63 and 64: MANUALE D’INSTALLAZIONE MODELLO N
- Page 65 and 66: Precauzioni di sicurezza Precauzion
- Page 67 and 68: Installare il condizionatore d’ar
- Page 69 and 70: Non installare l’unità esterna s
- Page 71 and 72: Avvertenze per l’esecuzione dei t
- Page 73 and 74: Combinazione con le unità interne
- Page 75 and 76: Spazio necessario attorno all’uni
- Page 77 and 78: Installazione multipla e installazi
- Page 79 and 80: Installazione Posizione del bullone
- Page 81 and 82: Installazione della tubatura refrig
- Page 83 and 84: Sistema di tubatura refrigerante
- Page 85 and 86: ◆ Metodo di diramazione del colle
- Page 87 and 88: ◆ Metodo di diramazione del colle
- Page 89 and 90: ◆ Tubo di collegamento unità int
- Page 91 and 92: A Installazione del tubo di diramaz
- Page 93 and 94: Test tenuta d’aria e fuoriuscite
- Page 95 and 96: Lavoro elettrico Avviso TB6 TB6 TB6
- Page 97 and 98: Linee di trasmissione e di alimenta
- Page 99 and 100: ◆ Esempio di collegamento del cav
- Page 101 and 102: ◆ Procedimento di indirizzamento
Preparation of Piping<br />
Appendix<br />
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.<br />
1) Cut the pipes and the cable.<br />
■ Use the accessory piping kit or the pipes purchased<br />
locally.<br />
■ Measure the distance between the indoor and the outdoor<br />
unit.<br />
■ Cut the pipes a little longer than measured distance.<br />
■ Cut the cable 1.5m longer than the pipe length.<br />
2) Burrs removal<br />
■ Completely remove all burrs from the cut cross section<br />
of pipe/tube.<br />
■ Put the end of the copper tube/pipe to downward direction<br />
as you remove burrs in order to avoid to let burrs<br />
drop in the tubing.<br />
3) Putting nut on<br />
■ Remove flare nuts attached to indoor and outdoor units,<br />
then put them on pipe/tube having completed burr<br />
removal.<br />
(Not possible to put them on after flaring work)<br />
4) Flaring work<br />
■ Carry out flaring work using flaring tool as shown below.<br />
Capacity<br />
Outside Diameter<br />
Gas Liquid Gas<br />
"A "<br />
Liquid<br />
18k Btu/h 5/8" 1/4" 0.8~1.0 0~0.5<br />
24k Btu/h 5/8" 1/4" 0.8~1.0 0~0.5<br />
30k Btu/h 5/8" 3/8" 0.8~1.0 0.5~0.8<br />
36k Btu/h 5/8" 3/8" 0.8~1.0 0.5~0.8<br />
42k Btu/h 3/4" 3/8" 1.0~1.3 0.5~0.8<br />
48k Btu/h 3/4" 3/8" 1.0~1.3 0.5~0.8<br />
60k Btu/h 3/4" 1/2" 1.0~1.3 0.5~0.8<br />
Firmly hold copper tube in a bar(or die) as indicated<br />
dimension in the table above.<br />
5) Check<br />
■ Compare the flared work with figure below.<br />
■ If flare is noted to be defective, cut off the flared section<br />
and do flaring work again.<br />
Copper<br />
tube 90° Slanted Uneven Rough<br />
Bar<br />
Point down<br />
Copper tube<br />
Copper pipe<br />
Smooth all round<br />
Even length<br />
all round<br />
"A"<br />
Pipe<br />
Flare nut<br />
Bar<br />
Clamp handle<br />
Inclined<br />
Reamer<br />
Handle<br />
Yoke<br />
Cone<br />
Red arrow mark<br />
Inside is shining without scratches.<br />
= Improper flaring =<br />
Surface Cracked Uneven<br />
damaged thickness<br />
Installation Manual 53<br />
ENGLISH