Self-Diagnosis Function<br />

Error Indicator<br />

Test Run<br />

• The function is to self-diagnose airconditioner and indicate the problems, if any.<br />

• Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of<br />

outdoor unit control board as shown in the table.<br />

• If more than two troubles occur simultaneously, lower number of error code is first displayed.<br />

• After error occurrence, if error is released, error LED is also released simultaneously.<br />

Indoor unit related error<br />

Power related error<br />

Compressor related error<br />

Display Title Cause of Error<br />

0 1 Indoor unit air sensor<br />

Indoor unit air sensor open or short<br />

0 2 Indoor unit sensor(inlet pipe) Indoor unit inlet pipe sensor open or short<br />

0 3<br />

Wired remote controller ↔ indoor<br />

unit transmission<br />

In the case that indoor unit can not receive any signal<br />

from wired remote controller successively for 3 minutes<br />

0 4 Drain pump<br />

Malfunction of drain pump<br />

0 5<br />

<strong>Outdoor</strong> unit ↔ indoor unit transmission<br />

In the case that indoor unit can not receive any signal<br />

from outdoor unit successively for 3 minutes<br />

0 6 Indoor unit outlet pipe sensor Indoor unit outlet pipe sensor open or short<br />

0 7 The other operation mode In the case that an indoor unit is operated the other<br />

operation mode different from the operated indoor unit<br />

0 8 Not in use<br />

Not in use<br />

0 9<br />

Serial No. Error<br />

In the case that the serial number marked on<br />

EEPROM of indoor unit is 0 or FFFFFF<br />

2 1<br />

DC peak<br />

IPM over temperature or compressor malfunction is<br />

occurred 3 times in 1 hour<br />

2 2<br />

Max CT<br />

When current detection is over the maximum current<br />

limit<br />

2 3<br />

DC link<br />

DC charging is not performed for 45 sec after starting<br />

relay turn on<br />

2 4 High pressure<br />

Compressor is OFF 3 times in 1 hour due to high pressure<br />

2 5<br />

Low/Over voltage<br />

Input voltage is out of tolerance of rating voltage<br />

3<br />

3<br />

3<br />

3<br />

3<br />

1<br />

2<br />

3<br />

4<br />

5<br />

Not in use<br />

Discharge temperature<br />

(inverter compressor)<br />

Discharge temperature<br />

(constant speed compressor)<br />

High pressure<br />

Low pressure<br />

Not in use<br />

Due to over rising of inverter compressor discharge temperature,<br />

Compressor off is occurred 3 times in 1 hour<br />

Due to over rising of constant speed compressor discharge<br />

temperature, Compressor off is occurred 3<br />

times in 1 hour<br />

Due to high pressure, Compressor off is occurred 3<br />

times in 1 hour<br />

Due to low pressure, Compressor off is occurred 3<br />

times in 1 hour<br />

Installation Manual 47<br />