Airtight Test and Evacuation<br />

(1) Airtight test<br />

Refrigerant piping installation<br />

Airtight test should be made by pressurizing nitrogen gas to 2.94 MPa. For the test method, refer to the following<br />

figure. (Make a test with the service valves closed. Be also sure to pressurize both liquid pipe and gas pipe.)<br />

The test result can be judged good if the pressure has not been reduced after leaving for about one day after<br />

completion of nitrogen gas pressurization.<br />

Charging<br />

cylinder<br />

Vacuum pump<br />

Indoor unit<br />

(1)<br />

(2) Evacuation<br />

Indoor unit<br />

Check valve<br />

Lo<br />

Lo<br />

Liquid side<br />

Gas side<br />

Liquid side<br />

Gas side<br />

3-Way<br />

valve<br />

3-Way<br />

valve<br />

3-Way<br />

valve<br />

<strong>Outdoor</strong> unit<br />

Evacuation should be made from the service port provided on the outdoor unit’s service valve to the vacuum<br />

pump commonly used for both liquid pipe and gas pipe. (Make evacuation from both liquid pipe and gas pipe<br />

with the service valve closed.)<br />

* Never perform air purging using refrigerant.<br />

<strong>Outdoor</strong> unit<br />

• Evacuation should be done for 3 hours or more<br />

after the pressure is under 5 tor.<br />

Scale<br />

Use a gravimeter. (One that can measure down to<br />

0.1 kg.). If you are unable to prepare such a highprecision<br />

gravimeter you may use a charge<br />

cylinder.<br />

Note : Always add an appropriate amount of refrigerant. (For the refrigerant additional charge)<br />

Too much or too little refrigerant will cause trouble.<br />

WARNING<br />

When installing and moving the air conditioner to another site, recharge after perfect evacuation.<br />

- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and<br />

the unit may be damaged.<br />