Refrigerant piping installation<br />

CRUN1008T0<br />

Example : 5 indoor units<br />

connected<br />

: outdoor unit<br />

: 1st branch<br />

(branch union)<br />

: Y branch<br />

: indoor unit<br />

: header<br />

: sealing<br />

: downward<br />

indoor unit<br />

➲ Piping diameter (A)<br />

- Liquid pipe : Ø15.88mm(5/8 inch)<br />

- Gas pipe : Ø28.58mm(9/8 inch)<br />

➲ Refrigerant pipe diameter from branch to branch (B,C)<br />

➲ Total pipe length = A+B+C+a+b+c+d+e ≤ 220m<br />

26 <strong>Outdoor</strong> <strong>Unit</strong><br />

50m<br />

H<br />

Downward indoor unit total capacity<br />

[kW(Btu/h)]<br />

~8.2(28,000)<br />

L<br />

l<br />

H<br />

h<br />

~17.6(60,000)<br />

~28.1(96,000)<br />

~36.3(125,000)<br />

Longest pipe length<br />

A+B+b ≤ 100m<br />

Longest pipe length after 1st branch<br />

B+b ≤ 30m<br />

A<br />

A<br />

B<br />

B<br />

Liquid pipe<br />

[mm(inch)]<br />

Ø9.52(3/8)<br />

Ø12.7(1/2)<br />

Ø12.7(1/2)<br />

Ø15.88(5/8)<br />

Difference in height(outdoor ↔ indoor)<br />

H ≤ 50m ( 40m : outdoor is lower than indoor units)*<br />

Difference in height (indoor ↔ indoor)<br />

h ≤ 15m<br />

* Indoor unit should be installed at lower position than the<br />

header<br />

C<br />

1<br />

C<br />

c<br />

d e<br />

3 D<br />

4 D 5 D<br />

L 100m<br />

l 30m<br />

b<br />

X<br />

E<br />

a 2<br />

D<br />

Branch pipe can not be used<br />

after header<br />

Gas pipe<br />

[mm(inch)]<br />

Ø15.88(5/8)<br />

Ø19.05(3/4)<br />

Ø25.4(1)<br />

Ø28.58(9/8)<br />

D<br />

F<br />

G<br />

15m<br />

h