Refrigerant piping installation<br />

CRUN1008T0<br />

Example : 6 indoor units<br />

connected<br />

: outdoor unit<br />

: 1st branch<br />

: indoor units<br />

: sealing<br />

➲ Piping diameter (A)<br />

- Liquid pipe : Ø15.88mm(5/8 inch)<br />

- Gas pipe : Ø28.58mm(9/8 inch)<br />

➲ Total pipe length = A+a+b+c+d+e+f ≤ 220m<br />

L<br />

l<br />

H<br />

h<br />

Longest pipe length<br />

A+f ≤ 100m<br />

24 <strong>Outdoor</strong> <strong>Unit</strong><br />

50m<br />

H<br />

A<br />

h<br />

Longest pipe length after 1st branch<br />

f ≤ 30m<br />

A<br />

15m<br />

Difference in height(outdoor ↔ indoor)<br />

a<br />

B<br />

C C<br />

1 2<br />

b<br />

c d<br />

C C<br />

3 4<br />

L 100m<br />

Branch pipe can not be used<br />

after header<br />

H ≤ 50m ( 40m : outdoor is lower than indoor units)*<br />

Difference in height (indoor ↔ indoor)<br />

h ≤ 15m<br />

* Indoor unit should be installed at lower position than the<br />

header<br />

X<br />

e<br />

C<br />

5<br />

D<br />

l 30m<br />

f<br />

C<br />

6