UK !!! 6. RS485 SERIAL LINE The MIR70 model can be connected, even afterwards, to a XJ500 monitoring and supervising system. This is possible thanks to the outputs for the XJRS485 external serial module that provides a standard output RS485. 7. ALARM SIGNALS Message Description Outputs “rEr” Remote control Outputs according to the external thermostat signals “PAL” Digital input alarm Alarm output ON; Other outputs OFF “P1” Cold room probe failure Alarm output ON; Compressor output according to "CSP" parameter “P2” Evaporator probe failure Alarm output ON; Other outputs unchanged; Timecontrolled defrost end “LA” Low temperature alarm Alarm output ON; Other outputs unchanged “HA” High temperature alarm Alarm output ON; Other outputs unchanged “EAL” Vacuum function error Alarm output ON; Other outputs OFF “noL” Missing data transmission between electronic control panel and keyboard All the signals different from the ones specified in this manual indicate a serious damage to the electronic control panel. 8. ALARM RECOVERY MODE The probe alarms "P1" and "P2" trip 30 seconds after the occurrence of a fault in the related probe; they stop automatically 30 seconds after the probe restarts normal operation. Check connections before replacing the probe. High and low temperature alarms stop automatically both as soon as the thermostat temperature returns to normal values and when defrost starts. The external alarm "PAL" stops, as soon as the external digital input is disconnected. 9. CONNECTION SCHEMES 20

10. PARAMETERS TABLE Label Description Range Unit Level Unit with capillary tube Unit with thermostatic valve REGULATION H-A M-N B-K H-A M-N B-K P-Q C-X Set Set point bSE ÷ tSE °C/°F — +10 0 -22 +10 0 -22 -22 -35 HyS SET differential (main one) -12,0 ÷ +12,0 °C/°F Pr1 2 2 2 2 2 2 2 2 bSE Minimum set point -60,0 ÷ tSE °C/°F Pr1 +5 -5 -25 +5 -5 -25 -25 -45 tSE Maximum set point bSE ÷ +300,0 °C/°F Pr1 +15 +5 -18 +15 +5 -18 +5 -25 Lrr Control by probe or digital input (D.I.) Prb/di Pr2 Prb Prb Prb Prb Prb Prb Prb Prb dbE Control activation by Neutral Zone n(0) ÷ y(1) Pr2 n n n n n n n n otd Output Delay at power-on (minimum) 0 ÷ 99 min Pr1 0 0 0 0 0 0 0 0 Sbd Stand-by function delay (0=function disabled) 0 ÷ 999 min Pr1 180 180 180 180 180 180 180 180 PPO Manual Activation delay by off/on key n / y Pr2 n n n n n n n n cPt Compressor protection type nP/don/do /dbi Pr2 doF doF doF doF doF doF doF doF cPr Compressor protection delay 0 ÷ 15 min Pr2 3 3 3 3 3 3 3 3 con Compressor running time through damaged probe 0 ÷ 99 min Pr2 30 30 30 30 30 30 30 30 coF Compressor OFF time through damaged probe 0 ÷ 99 min Pr2 10 10 10 10 10 10 10 10 SHt Regulation by thermostat probes P2 and P3 in neutral zone -60,0 ÷ +300,0 °C/°F Pr2 45 45 45 45 45 45 45 45 Hon DEF relay running time and/or DEF2 through damaged probe (P2,P3) 0 ÷ 99 min Pr2 5 5 5 5 5 5 5 5 HoF DEF relay OFF time and/or DEF2 through damaged probe (P2,P3) 0 ÷ 99 min Pr2 5 5 5 5 5 5 5 5 DEFROST dtP Defrost mode EL/in/Air Pr1 Air EL EL Air EL EL EL EL dtC Defrost with temperature control n / y Pr1 n y y n y y y y dEd Arranged for second evaporator connection n / y Pr2 n n n n n n n n din Defrost interval 0 ÷ 31 h Pr1 4 4 4 4 4 4 4 4 dcS Defrost interval counting mode dF/rt/SC Pr2 dF dF dF dF dF dF dF dF doF Defrost start offset 0 ÷ 59 min Pr2 0 0 0 0 0 0 0 0 dto Defrost time_out 1 ÷ 99 min Pr1 30 30 30 30 30 30 30 30 dEt Defrost termination temperature -60,0 ÷ +300,0 °C/°F Pr1 300 8 8 300 8 8 8 8 dti Drip time 0 ÷ 99 min Pr1 0 2 2 0 2 2 2 4 don Defrost at power-on n / y Pr2 n n n n n n n n dLo Display lockout during defrost n/y/lb/lg Pr2 n n n n n n n n dAd Display lockout maximum time after defrost 0 ÷ 120 min Pr2 0 0 0 0 0 0 0 0 FANS FPt "Fot" parameter mode Ab / rE Pr2 Ab Ab Ab Ab Ab Ab Ab Ab Fot Fan Stop Temperature -60,0 ÷ +300,0 °C/°F Pr1 40 40 40 40 40 40 40 40 Fdt Fan delay time after defrost 0 ÷ 99 min Pr1 0 3 3 0 3 3 3 5 dFo Fan override during defrost n / y Pr1 n y y n y y y y FSC Fan state by compressor off oF / on Pr1 oF oF oF oF oF oF oF on FSd Fan state by open door oF / on Pr1 oF oF oF oF oF oF oF oF ALARMS Att Parameters mode tAL and bAL: absolute or relative Ab / rE Pr2 rE rE rE rE rE rE rE rE tAL Maximum temperature alarm -60,0 ÷ +300,0 °C/°F Pr2 +10 +10 +10 +10 +10 +10 +10 +10 bAL Minimum temperature alarm -60,0 ÷ +300,0 °C/°F Pr2 -5 -5 -5 -5 -5 -5 -5 -5 Atd Temperature alarm signal delay 0 ÷ 120 min Pr1 0 0 0 0 0 0 0 0 AdF Alarm and fan Set differential 1 ÷ 50 °C/°F Pr2 2 2 2 2 2 2 2 2 Aoo Alarm override after power-on 0 ÷ 10 h Pr1 6 6 6 6 6 6 6 6 Aod Alarm override after defrost 0 ÷ 10 h Pr1 1 1 1 1 1 1 1 1 AoS Door opening alarm override 0 ÷ 10 h Pr1 1 1 1 1 1 1 1 1 AOP Output alarm polarity oP / CL Pr2 CL CL CL CL CL CL CL CL DIGITAL INPUTS Pnn Max. acceptable error nr. of pressure switch 0 ÷ 15 num Pr2 10 10 10 10 10 10 10 10 Pty Errors counting interval Alarm module/pressure switch 1 ÷ 99 min Pr2 60 60 60 60 60 60 60 60 EFd Vacuum function delay (from D.I.) 0 ÷ 99 min Pr1 0 0 0 10 10 10 10 10 Ldd Light /door keys active by device OFF n / y Pr2 y y y y y y y y dSo Door microswitch switches off unit n / y Pr2 y y y y y y y y dSL Door light switching on n / y Pr2 y y y y y y y y iP1 Polarity of the digital input 1 oP / CL Pr2 oP oP oP oP oP oP oP oP iP2 Polarity of the digital input 2 oP / CL Pr2 CL CL CL CL CL CL CL CL iP3 Polarity of the digital input 3 oP / CL Pr2 CL CL CL CL CL CL CL CL iP4 Polarity of the digital input 4 oP / CL Pr2 CL CL CL CL CL CL CL CL PROBES AND DISPLAYS PbC Probe input type: ptc or ntc PtC / ntC Pr2 ntC ntC ntC ntC ntC ntC ntC ntC C-F Celsius/fahrenheit display °C / °F Pr2 °C °C °C °C °C °C °C °C OF1 Probe 1 calibration -12,0 ÷ +12,0 °C/°F Pr2 0 0 0 0 0 0 0 0 P2P Evaporator probe presence n / y Pr1 n y y n y y y y OF2 Probe 2 calibration -12,0 ÷ +12,0 °C/°F Pr2 0 0 0 0 0 0 0 0 S2r Probe 2 read-out probe evap. Pr2 / / / / / / / / P3P Probe 3 presence n / y Pr2 n n n n n n n n P3F Probe 3 function selection dF2 / Ao Pr2 dF2 dF2 dF2 dF2 dF2 dF2 dF2 dF2 S3r Probe 3 read-out probe aux. Pr2 / / / / / / / / OF3 Probe 3 calibration -12,0 ÷ +12,0 °C/°F Pr2 0 0 0 0 0 0 0 0 ndt Number display: whole, decimals, half numbers int(0) - dEc(1) - hFn(2) Pr2 int int int int int int int int ANALOG OUTPUT SAo Set rpobe Analogue Output -60,0 ÷ +300,0 °C/°F Pr2 30 30 30 30 30 30 30 30 HAo Proportional band Analogue output -99 ÷ 99 °C/°F Pr2 15 15 15 15 15 15 15 15 LAO Minimum output analogue output 4 ÷ 15 mA Pr2 4 4 4 4 4 4 4 4 OTHER dEA Remote control device address 0 ÷ 14 num Pr2 0 0 0 0 0 0 0 0 FAA Remote control device family 0 ÷ 14 num Pr2 0 0 0 0 0 0 0 0 Loc Keyboard lockout n / y Pr2 n n n n n n n n PAS PASSWORD 0 ÷ 999 num Pr2 321 321 321 321 321 321 321 321 tiP Read_out release firmware 1 ÷ 999 Pr2 / / / / / / / / rEL Configuration table Index 1 ÷ 999 Pr2 / / / / / / / / 21 UK

10. PARAMETERS TABLE<br />

Label Description Range Unit Level Unit with capillary tube Unit with thermostatic valve<br />

REGULATION<br />

H-A M-N B-K H-A M-N B-K P-Q C-X<br />

Set Set point bSE ÷ tSE °C/°F — +10 0 -22 +10 0 -22 -22 -35<br />

HyS SET differential (main one) -12,0 ÷ +12,0 °C/°F Pr1 2 2 2 2 2 2 2 2<br />

bSE Minimum set point -60,0 ÷ tSE °C/°F Pr1 +5 -5 -25 +5 -5 -25 -25 -45<br />

tSE Maximum set point bSE ÷ +300,0 °C/°F Pr1 +15 +5 -18 +15 +5 -18 +5 -25<br />

Lrr Control by probe or digital input (D.I.) Prb/di Pr2 Prb Prb Prb Prb Prb Prb Prb Prb<br />

dbE Control activation by Neutral Zone n(0) ÷ y(1) Pr2 n n n n n n n n<br />

otd Output Delay at power-on (minimum) 0 ÷ 99 min Pr1 0 0 0 0 0 0 0 0<br />

Sbd Stand-by function delay (0=function disabled) 0 ÷ 999 min Pr1 180 180 180 180 180 180 180 180<br />

PPO Manual Activation delay by off/on key n / y Pr2 n n n n n n n n<br />

cPt Compressor protection type nP/don/do /dbi Pr2 doF doF doF doF doF doF doF doF<br />

cPr Compressor protection delay 0 ÷ 15 min Pr2 3 3 3 3 3 3 3 3<br />

con Compressor running time through damaged probe 0 ÷ 99 min Pr2 30 30 30 30 30 30 30 30<br />

coF Compressor OFF time through damaged probe 0 ÷ 99 min Pr2 10 10 10 10 10 10 10 10<br />

SHt Regulation by thermostat probes P2 and P3 in neutral zone -60,0 ÷ +300,0 °C/°F Pr2 45 45 45 45 45 45 45 45<br />

Hon DEF relay running time and/or DEF2 through damaged probe (P2,P3) 0 ÷ 99 min Pr2 5 5 5 5 5 5 5 5<br />

HoF DEF relay OFF time and/or DEF2 through damaged probe (P2,P3) 0 ÷ 99 min Pr2 5 5 5 5 5 5 5 5<br />

DEFROST<br />

dtP Defrost mode EL/in/Air Pr1 Air EL EL Air EL EL EL EL<br />

dtC Defrost with temperature control n / y Pr1 n y y n y y y y<br />

dEd Arranged for second evaporator connection n / y Pr2 n n n n n n n n<br />

din Defrost interval 0 ÷ 31 h Pr1 4 4 4 4 4 4 4 4<br />

dcS Defrost interval counting mode dF/rt/SC Pr2 dF dF dF dF dF dF dF dF<br />

doF Defrost start offset 0 ÷ 59 min Pr2 0 0 0 0 0 0 0 0<br />

dto Defrost time_out 1 ÷ 99 min Pr1 30 30 30 30 30 30 30 30<br />

dEt Defrost termination temperature -60,0 ÷ +300,0 °C/°F Pr1 300 8 8 300 8 8 8 8<br />

dti Drip time 0 ÷ 99 min Pr1 0 2 2 0 2 2 2 4<br />

don Defrost at power-on n / y Pr2 n n n n n n n n<br />

dLo Display lockout during defrost n/y/lb/lg Pr2 n n n n n n n n<br />

dAd Display lockout maximum time after defrost 0 ÷ 120 min Pr2 0 0 0 0 0 0 0 0<br />

FANS<br />

FPt "Fot" parameter mode Ab / rE Pr2 Ab Ab Ab Ab Ab Ab Ab Ab<br />

Fot Fan Stop Temperature -60,0 ÷ +300,0 °C/°F Pr1 40 40 40 40 40 40 40 40<br />

Fdt Fan delay time after defrost 0 ÷ 99 min Pr1 0 3 3 0 3 3 3 5<br />

dFo Fan override during defrost n / y Pr1 n y y n y y y y<br />

FSC Fan state by compressor off oF / on Pr1 oF oF oF oF oF oF oF on<br />

FSd Fan state by open door oF / on Pr1 oF oF oF oF oF oF oF oF<br />

ALARMS<br />

Att Parameters mode tAL and bAL: absolute or relative Ab / rE Pr2 rE rE rE rE rE rE rE rE<br />

tAL Maximum temperature alarm -60,0 ÷ +300,0 °C/°F Pr2 +10 +10 +10 +10 +10 +10 +10 +10<br />

bAL Minimum temperature alarm -60,0 ÷ +300,0 °C/°F Pr2 -5 -5 -5 -5 -5 -5 -5 -5<br />

Atd Temperature alarm signal delay 0 ÷ 120 min Pr1 0 0 0 0 0 0 0 0<br />

AdF Alarm and fan Set differential 1 ÷ 50 °C/°F Pr2 2 2 2 2 2 2 2 2<br />

Aoo Alarm override after power-on 0 ÷ 10 h Pr1 6 6 6 6 6 6 6 6<br />

Aod Alarm override after defrost 0 ÷ 10 h Pr1 1 1 1 1 1 1 1 1<br />

AoS Door opening alarm override 0 ÷ 10 h Pr1 1 1 1 1 1 1 1 1<br />

AOP Output alarm polarity oP / CL Pr2 CL CL CL CL CL CL CL CL<br />

DIGITAL INPUTS<br />

Pnn Max. acceptable error nr. of pressure switch 0 ÷ 15 num Pr2 10 10 10 10 10 10 10 10<br />

Pty Errors counting interval Alarm module/pressure switch 1 ÷ 99 min Pr2 60 60 60 60 60 60 60 60<br />

EFd Vacuum function delay (from D.I.) 0 ÷ 99 min Pr1 0 0 0 10 10 10 10 10<br />

Ldd Light /door keys active by device OFF n / y Pr2 y y y y y y y y<br />

dSo Door microswitch switches off unit n / y Pr2 y y y y y y y y<br />

dSL Door light switching on n / y Pr2 y y y y y y y y<br />

iP1 Polarity of the digital input 1 oP / CL Pr2 oP oP oP oP oP oP oP oP<br />

iP2 Polarity of the digital input 2 oP / CL Pr2 CL CL CL CL CL CL CL CL<br />

iP3 Polarity of the digital input 3 oP / CL Pr2 CL CL CL CL CL CL CL CL<br />

iP4 Polarity of the digital input 4 oP / CL Pr2 CL CL CL CL CL CL CL CL<br />

PROBES AND DISPLAYS<br />

PbC Probe input type: ptc or ntc PtC / ntC Pr2 ntC ntC ntC ntC ntC ntC ntC ntC<br />

C-F Celsius/fahrenheit display °C / °F Pr2 °C °C °C °C °C °C °C °C<br />

OF1 Probe 1 calibration -12,0 ÷ +12,0 °C/°F Pr2 0 0 0 0 0 0 0 0<br />

P2P Evaporator probe presence n / y Pr1 n y y n y y y y<br />

OF2 Probe 2 calibration -12,0 ÷ +12,0 °C/°F Pr2 0 0 0 0 0 0 0 0<br />

S2r Probe 2 read-out probe evap. Pr2 / / / / / / / /<br />

P3P Probe 3 presence n / y Pr2 n n n n n n n n<br />

P3F Probe 3 function selection dF2 / Ao Pr2 dF2 dF2 dF2 dF2 dF2 dF2 dF2 dF2<br />

S3r Probe 3 read-out probe aux. Pr2 / / / / / / / /<br />

OF3 Probe 3 calibration -12,0 ÷ +12,0 °C/°F Pr2 0 0 0 0 0 0 0 0<br />

ndt Number display: whole, decimals, half numbers int(0) - dEc(1) - hFn(2) Pr2 int int int int int int int int<br />

ANALOG OUTPUT<br />

SAo Set rpobe Analogue Output -60,0 ÷ +300,0 °C/°F Pr2 30 30 30 30 30 30 30 30<br />

HAo Proportional band Analogue output -99 ÷ 99 °C/°F Pr2 15 15 15 15 15 15 15 15<br />

LAO Minimum output analogue output 4 ÷ 15 mA Pr2 4 4 4 4 4 4 4 4<br />

OTHER<br />

dEA Remote control device address 0 ÷ 14 num Pr2 0 0 0 0 0 0 0 0<br />

FAA Remote control device family 0 ÷ 14 num Pr2 0 0 0 0 0 0 0 0<br />

Loc Keyboard lockout n / y Pr2 n n n n n n n n<br />

PAS PASSWORD 0 ÷ 999 num Pr2 321 321 321 321 321 321 321 321<br />

tiP Read_out release firmware 1 ÷ 999 Pr2 / / / / / / / /<br />

rEL Configuration table Index 1 ÷ 999 Pr2 / / / / / / / /<br />

21<br />