Aoo Alarm override after Power-on: (0÷10h) Temperature alarm override duration after the instrument switching on, both<br />

executed manually through the ON/OFF key or due to a power failure. The alarm remains inhibited for the time programmed.<br />

Aod Alarm override after defrost: (0÷10h) Temperature alarm override time after the defrost end. The alarm remains inhibited<br />

for the time programmed.<br />

AoS Door opening alarm override: (0÷10h) Temperature alarm override duration after door opening. The alarm remains<br />

deactivated during the time programmed.<br />

AOP Alarm relay output staate: CL: activated = closed ; oP: activated = open.<br />

DIGITAL INPUTS<br />

Pnn Number of signals of the alarm module: (0÷15) In the interval time set at the "Pty" parameter, number of signals of the<br />

alarm module that causes the alarm signalling and the disconnection of the compressor fan and defrost outputs. If the value set<br />

at this parameter is equal to zero, the function is disconnected and no pressure switch alarm is given.<br />

Pty Counting interval of the alarm module signals: (1÷99 min) Time interval during which the counting of the alarm<br />

module signals is effected.<br />

EFd Vacuum function delay: (1÷99min) Delay time between the compressor relay switching and the state change of the vacuum<br />

digital input.<br />

Ldd Light/door keys ON by device OFF: It determines if the light key and the door microswitch are on, even if the instrument<br />

is off but supplied. n= the keys do not work; y= the keys work.<br />

dSo Door microswitch switches off unit: Under the control of the door microswitch, it allows the unit switching off at the door<br />

opening. It switches on again after the door closing. Any protection delay is respected anyway (e.g. delay at compressor<br />

starting). n= it does not switch off the unit; y= it switches off the unit.<br />

dSL Door light switching on: Under the control of the door microswitch, this parameter allows the light switching on (if it was<br />

switched off) at door opening and its switching off at door closing. See also the "Idd" parameter.<br />

n= by open door the light does not switch on; y= by open door the light switches on.<br />

iP1 Polarity of the digital input 1: (door microswitch) CL= the digital input is activated when the contact is closed; oP= the<br />

digital input is activated if the contact is open.<br />

iP2 Polarity of the digital input 2: (alarm module) CL= the digital input is activated when the contact is closed; oP= the digital<br />

input is activated if the contact is open.<br />

iP3 Polarity of the digital input 3: (vacuum alarm) CL= the digital input is activated when the contact is closed; oP= the digital<br />

input is activated if the contact is open.<br />

iP4 Polarity of the digital input 4: (external control) CL= the digital input is activated when the contact is closed; oP= the digital<br />

input is activated if the contact is open.<br />

PROBES AND DISPLAYS<br />

PbC Selection of probe type: Ptc= PTC probe; ntc= NTC probe.<br />

C-F Celsius/Fahrenheit display: Through this parameter, it is possible to choose if the temperature value read by the probes has<br />

to be expressed in Celsius or Fahrenheit grades. In case this parameter is changed from °C to °F or vice versa, the set values,<br />

the differential etc. are not modified (e.g. if the programmed set is 10°C, by changing the display from °C to °F, the set will be 10°F).<br />

OF1 Thermostat probe calibration: (-12÷12°C) Positive or negative temperature offset that is added to the value read by the<br />

temperature control probe before it is displayed. The cold room temperature controller and the corresponding set points are linked<br />

to the value displayed. The offset value is programmable with the same unit of measurement of the display.<br />

P2P Evaporator probe presence: (Probe 2) n= probe not present (only time-controlled defrosts); y= probe present (defrost end<br />

due to temperature).<br />

OF2 Evaporator probe calibration: (-12÷12°C) Positive or negative temperature offset that is added to the value read by the<br />

evaporator probe.<br />

S2r Evaporator probe read: Display of the temperature read by the evaporator temperature probe.<br />

P3P Presence of the third probe: n= probe not present; y= probe present.<br />

P3F Function of the third probe: dF2= second evaporator. It reads the temperature of the second evaporator; Ao= it acts as digital output.<br />

S3r Read of the third probe: Display of the temperature read by the third temperature probe.<br />

OF3 Calibration of the third probe: (-12÷12°C) Positive or negative temperature offset that is added to the value read by the third probe.<br />