UK<br />

3 By pressing and releasing the key, it is displayed alternatively the parameter value or its label.<br />

ACCESS PROCEDURE TO "Pr2"<br />

To enter the parameters of the Pr2 level it necessary to write a password.<br />

1 Enter the programming by pressing the PRG key for some seconds;<br />

2 When rEL label is displayed, press again the PRG key for some seconds;<br />

3 The "Pr2" label appears followed by “PAS”;<br />

4 Press and use the keys and in order to write the correct number;<br />

5 Confirm this number by pushing key;<br />

6 If the password is correct, the "Pr2" is entered by pressing key, otherwise the password input process restarts from the<br />

beginning.<br />

If no key is pressed within 15 seconds, the instrument displays the ambient probe temperature. <br />

N.B.: Each parameter in "Pr2" can be removed or put into the user level by pressing the PRG key for some seconds when<br />

you are in "Pr2". If a parameter is present only in "Pr2", its label blinks.<br />

PASSWORD: The password to enter the parameters present in Pr2 is defined by the parameter PAS.<br />

Anyway, it exists a safety password: 981.<br />

4. LIST OF THE PARAMETERS<br />

REGULATION<br />

HyS Control differential ON/OFF: (-12,0÷+12,0) Intervention differential for set point, always positive. The compressor cuts in<br />

when the temperature reaches the Set Point + HyS value. It cuts OUT when the temperature reaches again the set point value.<br />

bSE Minimum set point: (-60,0÷TsE) Sets the minimum acceptable value for the cold room temperature set point.<br />

tSE Maximum set point: (bSE÷300,0) Sets the maximum acceptable value for the cold room temperature set point.<br />

Lrr Control by probe or digital input: (D.I.) Prb= Control by probe; di= Control by digital input.<br />

dbE Neutral zone activated: n = standard functioning; y = neutral zone function activated.<br />

otd Output Delay at power-on: (0÷99 min) Shortest instrument start delay time in case of restart after a power failure.<br />

As concerns the Light Relay, this delay is never programmed.<br />

Sbd Standby function: (0÷999 min) Control activation delay after ON/off key pressing.<br />

PPO Manual Activation delay by off/on key: n= at the end of Sbd the control starts; y= at the end of Sbd the otd delay is charged.<br />

cPt Compressor protection type: It indicates which kind type of protection is activated on compressor relay implementations. In<br />

any case, it is present a minimum 4 second relay on compressor relay switching.<br />

np= no protection; don= delay at starting; doF= delay after switching off; dbi= delay between startings.<br />

cPr Compressor protection delay: (0÷15 min) Delay time or interval concerning the selection effected at the "cPt" parameter.<br />

Even if a value equal to zero is programmed, a 4 second protection interval between the trippings remains always enabled. If<br />

the "cPt" parameter is equal to "nP", this parameter is ignored.<br />

con Compressor running time during Duty_cycle: (0÷99 min). This parameter is used in case of control probe failure and the<br />

compressor control mode is foreseen in Duty Cycle. It indicates the time interval during which the compressor is on.<br />

coF Compressor OFF time during Duty_cycle: (0÷99 min). This parameter is used in case of control probe failure.<br />

The compressor control mode is foreseen in Duty Cycle. It is the time interval during which the compressor is off.<br />

SHt Set point controlled by themostat probes P2 and P3 in neutral zone: (-60,0 ÷ +300,0 °C) the temperatures of<br />

reference are the ones read by probes no. 2 and no. 3. The relay reset differential is provided by Adf parameter. If the second<br />

evaporator is activated (dEd=y), but the P3P = n parameters or P3F = Ao or probe no. 3 are damaged, the second evaporator<br />

is cyclically excited with the times given by Hon = on time and Hof = off time parameters.<br />

Hon DEF and/or DEF2 ON time because of damaged probe (P2, P3): (0 ÷ +99 min) Time during which DEF and or DEF2<br />

relays are activate in case of damaged probe.<br />

HoF DEF and/or DEF2 OFF time because of damaged probe (P2, P3): (0 ÷ +99 min) Time during which DEF and or DEF2<br />

relays are disconnected in case of damaged probe.<br />

16