Hardware<br />

3.4.4 Analogue Outputs<br />

Ventura Remote PLC has 2 analogue outputs labelled<br />

ao0, and ao1. They are set by the configuration. Their<br />

resolution can be set to either 8 bit (10V/256, i.e. approx.<br />

39mV) or 10 bit (10V/1024, i.e. approx. 96mV). They<br />

attach to the screw-type locking terminal. Immediately<br />

next to the analogue input, there is a terminal for the<br />

analogue reference potential. All analogue reference<br />

potential terminals are interconnected.<br />

ao<br />

1<br />

0<br />

Signal pin wiring<br />

The screw-type locking terminals<br />

are safe for use with conductors of<br />

a diameter between 0.25 mm 2 and<br />

1.5 mm 2 .<br />

To avoid noise on the operative<br />

signal, you are advised to use<br />

shielded cables. Attach the shield<br />

to the earth conductor terminals on<br />

the left side wall.<br />

40 E 700 GB