3.3 Power Supply<br />

3.3.1 Earth<br />

left side wall<br />

Hardware<br />

The metal housing has to be connected to earth. Use the<br />

earth conductor located on the left side wall.<br />

� Earth conductor<br />

Cross section: min. 2.5 mm²<br />

Length: as short as possible<br />

� Interfacing<br />

Flat plug 6.3 x 0.8 mm<br />

� Function<br />

The earth conductor serves as operative earth<br />

(special case: relay module � E 409 GB).<br />

The +24 VDC and 0 V power supply connectors have<br />

an internal (by spring-actuated contacts on the PCB)<br />

capacitive connection to the housing which also<br />

attaches them to earth. Line-conducted HF<br />

interference is bled off into the ground.<br />

The PROFIBUS plug connector housing directly<br />

connects to operative earth which is where the cable<br />

shield is attached also.<br />

This earth conductor is no protection against high contact<br />

voltage. To provide sufficient protection, supply the<br />

devices with properly separated low voltage.<br />