Error Handling<br />

8.3.2 Low Voltage (Power Supply, Error #2)<br />

Supply voltage: 24 VDC -20%/+20%<br />

The integrated voltage monitor has a two-stage reaction<br />

to voltages dropping below set limits:<br />

1st stage<br />

Cause supply voltage drops to approx. < 17.5 V<br />

Reaction<br />

� ERROR_IRQ_module is run (see page 82)<br />

� The program keeps running for the time being<br />

Variables may be reset unintentionally if the user program<br />

continues to run at this stage. This would be caused by<br />

remote inputs already detecting a 0 signal due to the low<br />

voltage.<br />

Indication<br />

� "failure" LED flashes (2x)<br />

� Bit 1 in "SYSTEMINFO.ERROR" is set<br />

2nd stage<br />

First alternative<br />

Cause<br />

The voltage goes back up to 24 VDC ± 20%<br />

Reaction<br />

� "failure" LED stops flashing<br />

� Bit 1 in "SYSTEMINFO.ERROR" is reset<br />

� The program keeps running without interruption<br />

Second alternative<br />

Cause<br />

The supply voltage keeps dropping further to < 7 V<br />

Reaction<br />

The 5 V system voltage is interrupted<br />

182 E 700 GB