6.2.4 Master-Slave Data Communication<br />
PROFIBUS<br />
Following successful initialisation, the master starts<br />
exchanging data always repeating the same routine:<br />
Sent by Frame Recipient<br />
master sends output data slave<br />
slave sends input data master<br />
The volume of data transferred is specified when<br />
configuring the master project.<br />
The maximum transfer volume is 100 words (200 byte)<br />
which can be made up of several data modules.<br />
Available modules<br />
In<br />
Length<br />
Out<br />
Module Name Consistency<br />
1 word 1 word Data in:1w / out: 1 w Total length<br />
4 words 4 words Data in:4w / out: 4 w Total length<br />
8 words 8 words Data in:8w / out: 8 w Total length<br />
16 words 16 words Data in:16w / out: 16 w Total length<br />
32 words 32 words Data in:32w / out: 32 w Word<br />
64 words 64 words Data in:64w / out: 64 w Word<br />
Ventura Remote PLC DP uses global variable DPSLAVE<br />
to store the data (inputs and outputs) plus the information<br />
about the configuration and the PROFIBUS status. The<br />
data type of DPSLAVE is SPC3_P690 which is defined in<br />
library P690.LIB.<br />
� Run the CoDeSys PLC Configuration Editor and<br />
display the Library Manager screen.<br />
� Choose P690.LIB and open folder "Data types".<br />