PROFIBUS<br />

Bit set by Explanation<br />

0 slave Diag.Prm_Req<br />

Octet 2: station_status_2<br />

DP slave parameters need to be set again<br />

1 slave Diag.Stat_Diag (static diagnosis)<br />

DP master to get diagnostic data<br />

2 slave Always set (=1)<br />

3 slave Diag.WD_On<br />

Watchdog (response timeout) enabled<br />

4 slave Diag.Freeze_Mode<br />

DP slave received a Freeze command<br />

5 slave Diag.Sync_Mode<br />

6 slave Reserved<br />

7<br />

master<br />

DP slave received a Sync command<br />

Diag.Deactivated<br />

The set of DP slave parameters marks the DP slave as<br />

inactive so that it is no longer included in the master's cyclic<br />

procedures<br />

Bit set by Explanation<br />

0<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7 slave<br />

Octet 3: station_status_3<br />

Reserved<br />

Diag.Ext_Diag_Overflow<br />

There is more diagnostic data than specified in the devicespecific<br />

diagnosis<br />

162 E 700 GB