PROFIBUS<br />

replaces the term "byte" with the term "octet" which is also<br />

the word used by the standard.<br />

A set bit (=1) signifies that the described event has<br />

occurred.<br />

6.2.3.1 Standard Diagnostic Data<br />

Bit set by Explanation<br />

Octet 1: station_status_1<br />

0 master Diag.Station_Non_Existent (not supported by <strong>Kuhnke</strong> masters)<br />

DP slave cannot be accessed via the bus<br />

1 slave Diag.Station_Not_Ready<br />

DP slave not ready for data exchange<br />

2 slave Diag.Cfg_Fault<br />

The last set of configuration data received from the master is<br />

not the same that the DP slave found<br />

3 slave Diag.Ext_Diag<br />

There is a device-specific diagnostic result (octet 7...)<br />

4 slave Diag.Not_Supported<br />

The requested information cannot be supplied by the DP slave<br />

5 master Diag.Invalid_Slave_Response<br />

The slave response is not plausible<br />

6 slave Diag.Param_Fault<br />

Bad telegram of parameter data sent<br />

7 master Diag.Master_Lock<br />

The DP slave parameters were set by another master<br />