PROFIBUS<br />
6.2.3 Send Diagnostic Data (Diag_Data)<br />
The set of diagnostic data informs the master of the status<br />
of the DP slave.<br />
DP slave message<br />
Usually the slave responds by sending a low-priority<br />
telegram to the master. However, if the DP slave finds an<br />
error, it sends the master a high-priority telegram. As long<br />
as the master does not respond accurately but continues<br />
data communication as before, the DP slave continues to<br />
send a high-priority telegram.<br />
Response from the master<br />
The master's appropriate response to a high-priority frame<br />
is to request the diagnostic data:<br />
Sent by Frame<br />
Recipient<br />
Unit SAP<br />
master request diagnostic data slave 60<br />
slave send diagnostic data master -<br />
After successful diagnosis, the master continues data<br />
communication unless other actions are started by the<br />
user program.<br />
All diagnostic data are sent to the master where they are<br />
mapped onto specific byte operands.<br />
In the case of <strong>Kuhnke</strong> masters<br />
� 645-500, 680I, PROFIBUS modules of system 680<br />
and 657P, the VEBES configuration utility is used to<br />
define this operand range.<br />
� 645-12M and 680V, KUBES module DP_CTRL is<br />
used to request and download the diagnostic data.<br />
� Ventura Slot PLC and PC Control 645-PCI-CoDeSys,<br />
function PbGetDiagnostics is run to download the<br />
diagnostic data.<br />
Six bytes (Octets 1...6) contain the standard diagnostic<br />
information of Ventura Remote I/O. Bytes 7...13 contain<br />
the device-specific diagnostic information. The text below<br />
160 E 700 GB