17.02.2013 Views

Kuhnke Electronics Instruction Manual

Kuhnke Electronics Instruction Manual

Kuhnke Electronics Instruction Manual

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

5.3.6 Internal Analogue Output Functions<br />

Ventura Remote PLC has:<br />

� 2 analogue outputs ao0 and ao1<br />

Software<br />

� Analogue outputs send analogue control signals to<br />

drives etc. in order to control and actuate them.<br />

Analogue outputs are designed as PWM outputs.<br />

The voltage is set by the pulse-to-pause ratio plus<br />

subsequent smoothing.<br />

The resolution is used to set the output frequency<br />

and, with it, the range of output voltages:<br />

Resolution<br />

(Aufloesung)<br />

Number of<br />

output values<br />

Frequency<br />

[kHz]<br />

Ripple<br />

8 bit 256 62.5 ±5mV<br />

10 bit 1024 15.625 ±10mV<br />

� To set up the resolution of every analogue output and<br />

to retrieve information about analogue output<br />

variables, choose "Resources, PLC Configuration,<br />

<strong>Kuhnke</strong> Ventura Remote IO CAN (or DP), Internal IO,<br />

AO 2".<br />

Analogue output: resolution<br />

� Disable unused analogue outputs via the PLC<br />

Configuration Editor.<br />

141

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!