Software Measuring range Number of digital values Range of values 0..+5 V 1024 0..16#7FE0 0..+10 V 1024 0..16#7FE0 Sample program: The measuring range of channel 3 is set to 10V. ai3 measures +10.0V. 140 E 700 GB

5.3.6 Internal Analogue Output Functions Ventura Remote PLC has: � 2 analogue outputs ao0 and ao1 Software � Analogue outputs send analogue control signals to drives etc. in order to control and actuate them. Analogue outputs are designed as PWM outputs. The voltage is set by the pulse-to-pause ratio plus subsequent smoothing. The resolution is used to set the output frequency and, with it, the range of output voltages: Resolution (Aufloesung) Number of output values Frequency [kHz] Ripple 8 bit 256 62.5 ±5mV 10 bit 1024 15.625 ±10mV � To set up the resolution of every analogue output and to retrieve information about analogue output variables, choose "Resources, PLC Configuration, Kuhnke Ventura Remote IO CAN (or DP), Internal IO, AO 2". Analogue output: resolution � Disable unused analogue outputs via the PLC Configuration Editor. 141

Software<br />

Measuring<br />

range<br />

Number of<br />

digital values<br />

Range of<br />

values<br />

0..+5 V 1024 0..16#7FE0<br />

0..+10 V 1024 0..16#7FE0<br />

Sample program:<br />

The measuring range of channel 3 is set to 10V.<br />

ai3 measures +10.0V.<br />

140 E 700 GB