5.3.4 Short-circuited Output<br />
Software<br />
Overload fuses out the outputs thermally. This section<br />
describes an extra, software-controlled short circuit<br />
monitoring which is available for normal outputs but not<br />
for clock pulse outputs, though.<br />
5.3.4.1 Combi Outputs di0...do3 (SO_0...SO_3)<br />
A short-circuited output is turned off by the PLC. To undo<br />
the switch-off you must first restart the PLC or choose<br />
Online-CoDeSys-Reset. The short circuit error indicated<br />
by the error LED will be reset only when you restart the<br />
controller.<br />
Getting the input states back from the inputs allows you to<br />
check the PLC program for the output that was actually<br />
short-circuited.<br />
Getting the input states back from the inputs allows you<br />
to check the PLC program for the output that was actually<br />
short-circuited.<br />
5.3.4.2 Digital Outputs of the Basic Module<br />
A short-circuited output is turned off by a thermal fuse.<br />
5.3.4.3 Interrupt Following Short Circuit<br />
A short circuit to do0 ... do3 will generate an interrupt<br />
request to the PLC. To allocate program code to the<br />
interrupt request run function INSTALL_ERROR_IRQ<br />
(� 4.4.6)<br />
The module should contain the code to respond to the<br />
request, e.g. to turn off some major or all outputs using<br />
function ENADIS_OUTPUTS (� 4.4.3)<br />