4.7.2 Variables with Set Addresses<br />

4.7.2.1 Local Inputs and Outputs<br />

Group Input Function Type Qty<br />

I<br />

Q<br />

%IX0.0 inputs 16/32 %IX0.0<br />

Input Range<br />

from to<br />

%IX0.15<br />

(%IX1.15)<br />

PROFIBUS-DP<br />

Comment<br />

standard IN<br />

%IX12.0 inputs 4 %IX12.0 %IX12.3 interrupt IN<br />

%QX0.0 outputs 16/32 %QX0.0 %QX0.15<br />

BOOL<br />

(%QX1.15)<br />

standard OUT<br />

%QX10.0 outputs<br />

4 %QX0.0 %QX10.3<br />

special/clock<br />

OUT<br />

I %IW2 inputs 4 %IW2 %IW5 analogue IN<br />

Q %QW2 outputs<br />

WORD<br />

2 %QW2 %QW3 analogue OUT<br />

Q %QW8 parameter<br />

2 %QW8 %QW9<br />

clock output<br />

frequency<br />

I %ID3 parameter 3 %ID3 %ID5 counter<br />

Q %QD2 parameter DWORD<br />

2 %QD2 %QD3 counter<br />

4.7.2.2 Internal Markers<br />

Group Input Function Type Qty<br />

Input Range<br />

from to<br />

MX %MX0.0 BOOL 2048 %MX0.0 %MX2047.15<br />

MB %MB0 BYTE 4096 %MB0 %MB4095<br />

Marker<br />

MW %MW0 WORD 2048 %MW0 %MW2047<br />

MD %MD0<br />

DWORD 1024 %MD0 %MD1023<br />

Comment<br />

There is a marker range exactly 4096 byte in size.<br />

MX, MB, MW and MD are just different ways of accessing<br />

the same marker range.<br />

The first byte in a word is byte #0.<br />

Bits are stored by word. The first bit in a word is bit #0.<br />

115