4.7.2 Variables with Set Addresses<br />
4.7.2.1 Local Inputs and Outputs<br />
Group Input Function Type Qty<br />
I<br />
Q<br />
%IX0.0 inputs 16/32 %IX0.0<br />
Input Range<br />
from to<br />
%IX0.15<br />
(%IX1.15)<br />
PROFIBUS-DP<br />
Comment<br />
standard IN<br />
%IX12.0 inputs 4 %IX12.0 %IX12.3 interrupt IN<br />
%QX0.0 outputs 16/32 %QX0.0 %QX0.15<br />
BOOL<br />
(%QX1.15)<br />
standard OUT<br />
%QX10.0 outputs<br />
4 %QX0.0 %QX10.3<br />
special/clock<br />
OUT<br />
I %IW2 inputs 4 %IW2 %IW5 analogue IN<br />
Q %QW2 outputs<br />
WORD<br />
2 %QW2 %QW3 analogue OUT<br />
Q %QW8 parameter<br />
2 %QW8 %QW9<br />
clock output<br />
frequency<br />
I %ID3 parameter 3 %ID3 %ID5 counter<br />
Q %QD2 parameter DWORD<br />
2 %QD2 %QD3 counter<br />
4.7.2.2 Internal Markers<br />
Group Input Function Type Qty<br />
Input Range<br />
from to<br />
MX %MX0.0 BOOL 2048 %MX0.0 %MX2047.15<br />
MB %MB0 BYTE 4096 %MB0 %MB4095<br />
Marker<br />
MW %MW0 WORD 2048 %MW0 %MW2047<br />
MD %MD0<br />
DWORD 1024 %MD0 %MD1023<br />
Comment<br />
There is a marker range exactly 4096 byte in size.<br />
MX, MB, MW and MD are just different ways of accessing<br />
the same marker range.<br />
The first byte in a word is byte #0.<br />
Bits are stored by word. The first bit in a word is bit #0.<br />
115