<strong>Fuxx</strong> <strong>Control</strong> <strong>ARS</strong> <strong>2320</strong> / <strong>ARS</strong> <strong>2340</strong> KUHNKE Automation<br />

The following steps show how to get a rotating drive to a “safe stop”:<br />

1. Before activating the “safe stop” (i.e. driver supply relay “OFF” and output stage enabling “OFF”;<br />

both shut-down paths inhibit the PWM signals) the drive should be stopped by deactivating the<br />

controller enabling. Depending on the application, the brake ramp (t9-t8) can be set via<br />

ServoCommander (“Quick stop deceleration”).<br />

Activation of the “safe stop” function during operation will cause the drive to run down. If<br />

the drive has a holding brake it will be activated. It is therefore very important to make<br />

sure that the motor brake can actually stop the motion of the drive.<br />

2. After 0 speed has been reached, the drive will be controlled to this set value for a parameterizable<br />

drop-out delay time (t10-t9). This parameterizable time is the deceleration, at which the holding<br />

brake of the motor is applied. This time depends on the holding brake and must be set by the<br />

user. For applications without holding brake this time can be set to 0.<br />

3. After this time has run out, the internal output stage enabling will be switched off by the µP (t10).<br />

The holding brake will definitely be activated as soon as the “brake ramp time + set drop-out delay<br />

time” has run out, even if it the drive has not yet been able to stop!<br />

4. As of t10 the “safe stop” can be activated (simultaneous deactivation of triggering of driver<br />

supply relay and output stage enabling). The time (t11-t10) depends on the application and<br />

must be set by the user.<br />

5. With the withdrawal of the trigger signal for the relay that switches off the driver supply<br />

(t11) the capacitors in this voltage branch will be discharged. Approx. 80ms (t12-t11) after<br />

the withdrawal of the trigger signal for the relay that switches off the driver supply, the<br />

feedback contact ([X3], pins 5 and 6) will be closed.<br />

6. At the time t13 the letter “H” will be shown on the 7-segment display of the servo controller<br />

for the visualization of the “safe stop” function. This will happen no later than 30ms after<br />

the closing of the floating feedback contact (t13-12).<br />