10.1.7 I²t monitoring<br />
The <strong>ARS</strong> 2300 servo positioning controller has an I²t monitoring system to limit the average power<br />
loss in the power output stage and in the motor. Since the power loss in the electronic power system<br />
and in the motor increases in a square manner with the current in the worst case, the squared current<br />
value is taken as the measure for the power loss.<br />
10.1.8 Power monitoring of the internal brake chopper<br />
The firmware includes an " I²t brake chopper" power monitoring system for the internal braking<br />
resistor.<br />
When the " I²t brake chopper" power monitoring system reaches a value of 100%, the power of the<br />
internal braking resistor is reset to nominal power.<br />
10.1.9 Start-up status<br />
Servo positioning controllers, which are sent to KUHNKE AUTOMATION GmbH & Co KG for service,<br />
will be equipped with a different firmware and different parameters for testing purposes.<br />
Before the <strong>ARS</strong> 2300 servo positioning controller is re-used for the first time at the end user, it has to<br />
be re-parameterized. The ServoCommander parameterization software inquires the start-up status<br />
and asks the user to parameterize the servo positioning controller. At the same time, the device<br />
displays an "A" on the seven-segment display to indicate that it is ready for operation but not<br />
parameterized.<br />
10.1.10 Rapid discharge of the DC-link<br />
If the system detects a failure of the mains supply, the DC-link is rapidly discharged within the safety<br />
period in accordance with EN 60204.<br />
Delayed activation of the brake chopper according to power classes in the case of parallel operation<br />
and mains supply failure ensures that the main energy during rapid discharge of the DC-link is taken<br />
over through the braking resistors of the higher power classes.<br />