KUHNKE Automation <strong>Fuxx</strong> <strong>Control</strong> <strong>ARS</strong> <strong>2320</strong> / <strong>ARS</strong> <strong>2340</strong><br />

10.1.7 I²t monitoring<br />

The <strong>ARS</strong> 2300 servo positioning controller has an I²t monitoring system to limit the average power<br />

loss in the power output stage and in the motor. Since the power loss in the electronic power system<br />

and in the motor increases in a square manner with the current in the worst case, the squared current<br />

value is taken as the measure for the power loss.<br />

10.1.8 Power monitoring of the internal brake chopper<br />

The firmware includes an " I²t brake chopper" power monitoring system for the internal braking<br />

resistor.<br />

When the " I²t brake chopper" power monitoring system reaches a value of 100%, the power of the<br />

internal braking resistor is reset to nominal power.<br />

10.1.9 Start-up status<br />

Servo positioning controllers, which are sent to KUHNKE AUTOMATION GmbH & Co KG for service,<br />

will be equipped with a different firmware and different parameters for testing purposes.<br />

Before the <strong>ARS</strong> 2300 servo positioning controller is re-used for the first time at the end user, it has to<br />

be re-parameterized. The ServoCommander parameterization software inquires the start-up status<br />

and asks the user to parameterize the servo positioning controller. At the same time, the device<br />

displays an "A" on the seven-segment display to indicate that it is ready for operation but not<br />

parameterized.<br />

10.1.10 Rapid discharge of the DC-link<br />

If the system detects a failure of the mains supply, the DC-link is rapidly discharged within the safety<br />

period in accordance with EN 60204.<br />

Delayed activation of the brake chopper according to power classes in the case of parallel operation<br />

and mains supply failure ensures that the main energy during rapid discharge of the DC-link is taken<br />

over through the braking resistors of the higher power classes.<br />

E 732 GB 117<br />