Appendix KUHNKE Automation<br />
10.2 Technical Data<br />
10.2.1 Basic Data<br />
Function........................................................ cabinet-mounted <strong>IPC</strong><br />
Design........................................................... installs on universal carrier rail in switching cabinet or on screw<br />
plate adapter<br />
Dimensions<br />
<strong>Ventura</strong> <strong>IPC</strong> 300.................................. 190x55x130 (WxHxD in mm)<br />
<strong>Ventura</strong> <strong>IPC</strong> 700.................................. 190x81x130 (WxHxD in mm)<br />
<strong>Ventura</strong> <strong>IPC</strong> 1000................................ 190x69x130 (WxHxD in mm)<br />
<strong>Ventura</strong> <strong>IPC</strong> + / FB .............................. 190x85x130 (WxHxD in mm)<br />
Weight<br />
<strong>Ventura</strong> <strong>IPC</strong> 300.................................. 1400g<br />
<strong>Ventura</strong> <strong>IPC</strong> 700.................................. 1800g<br />
<strong>Ventura</strong> <strong>IPC</strong> 1000................................ 1500g<br />
<strong>Ventura</strong> <strong>IPC</strong> 300 + / FB....................... 1800g<br />
Protection ................................................. IP 20 compliant to IEC 60529<br />
Protection class ........................................ class I compliant to IEC 61140<br />
Environment<br />
CE ............................................................. yes<br />
UL ............................................................. upon request<br />
PNO certificate (PROFIBUS) ................... upon request<br />
Power supply<br />
Supply voltage (DC) ................................ 24 VDC ±20% (19.2 to 28.8 V)<br />
Brief voltage interruption<br />
to Namur.............................................. Min. 15 ms (at 20.4 V).<br />
Max. 10 events per hour; recovery time min. 1s<br />
Power consumption at 24 VDC<br />
<strong>Ventura</strong> <strong>IPC</strong> 300.................................. 550 mA (typ. 450 mA)<br />
<strong>Ventura</strong> <strong>IPC</strong> 700.................................. 1000 mA (typ. 800 mA)<br />
Electromagnetic compatibility (EMC)<br />
Noise emission ......................................... EN 55022 Class B; FCC Class A<br />
Susceptibility to noise<br />
noise voltage conducted by ................<br />
power supply lines............................... +/- 2 kV compliant to IEC 61000-4-4; Burst.<br />
+/- 1 kV compliant to IEC 61000-4-5; symmetrical surge.<br />
+/- 2 kV compliant to IEC 61000-4-5; surge, asymmetrical<br />
signal lines........................................... +/- 1 kV compliant to IEC 61000-4-4; burst; length < 3 m<br />
+/- 2 kV compliant IEC 61000-4-4; burst; length > 3 m<br />
+/- 2 kV compliant IEC 61000-4-5; surge; length > 30 m<br />
discharge of static electricity ............... +/- 6 kV contact discharge to IEC 61000-4-2.<br />
+/- 8 kV air discharge to IEC 61000-4-2<br />
from HF interference ........................... 10 V/m 80 – 1000 MHz, 80% AM to IEC 61000-4-3.<br />
10 V/m 900 MHz and 1.89 GHz, 50% duty cycle to IEC 61000-<br />
4-3.<br />
10 V 9 KHz – 80 MHz, to IEC 61000-4-6<br />
Magnetic field ........................................... 30A/m 50 Hz compliant to IEC 61000-4-8<br />
64 E 674 GB<br />