3.15 Error Codes<br />
RUN<br />
STOP<br />
ERROR<br />
HDD<br />
BUS<br />
DVI<br />
USB<br />
RESET<br />
LEDs "RUN“, "STOP“ and "ERROR“ exclusively refer to functions of soft-<br />
PLC CoDeSys SP. If CoDeSys SP if off these LEDs have no function.<br />
LEDs "RUN" and "STOP", PLC op. modes<br />
RUN STOP Operating mode<br />
Off On PLC program not loaded<br />
Off On PLC program loaded but not started<br />
On Off PLC program loaded and started<br />
Flashing On PLC program loaded and started but stopped at<br />
breakpoint (DEBUG)<br />
LED "ERROR"<br />
Whereas LED "ERROR" indicates serious operative problems, it is not indicative<br />
of any PLC program errors. The following classify a serious operative<br />
problems: watchdog, low voltage, short circuit.<br />
If applicable, these problems are indicated by KUHNKE's well-known flash<br />
codes. Every flash pulse lasts 500 ms (250 ms on, 250 ms off), every flash<br />
sequence consists of n flash pulses (e.g. watchdog: n = 3), flash sequences<br />
are interrupted by 1 s breaks (off).<br />
30 E 674 GB<br />
07.03.2007