2.3. INTERFACES 8<br />
For adaptation <strong>to</strong> the corresponding process signals, various acquisition units are avail-<br />
able.<br />
VCDAU (Voltage/Current Data Acquisition Unit)<br />
[8 analog (4 x voltage / 4 x current) <strong>and</strong> 16 binary inputs]<br />
The unit is used <strong>to</strong> record current / voltage <strong>and</strong> binary inputs. Typical applications<br />
are the moni<strong>to</strong>ring <strong>of</strong> feeders or a transformer panel. The calculated measurements are<br />
derived from the input current <strong>and</strong> voltage.<br />
CDAU (Current Data Acquisition Unit)<br />
[8 analog (8 x current) <strong>and</strong> 16 binary inputs]<br />
The unit is used <strong>to</strong> record current <strong>and</strong> binary inputs. A typical application is the record-<br />
ing <strong>of</strong> two feeders.<br />
VDAU (Voltage Data Acquisition Unit)<br />
[8 analog (8 x voltage) <strong>and</strong> 16 binary inputs]<br />
The unit is used <strong>to</strong> record voltage <strong>and</strong> binary inputs. A typical application is the record-<br />
ing <strong>of</strong> busbar voltages.<br />
BDAU (Binary Data Acquisition Unit)<br />
[32 binary inputs]<br />
This unit is used whenever 16 binary inputs per analog acquisition module are insuffi-<br />
cient. This allows the user, for example <strong>to</strong> combine 8 analog <strong>and</strong> 48 binary inputs.<br />
DDAU (DC Data Acquisition Unit)<br />
[8 analog (8 x process measur<strong>and</strong>s) <strong>and</strong> 16 binary inputs]<br />
The unit is used <strong>to</strong> record process measurements, such as 4 <strong>to</strong> 20 mA, or DC voltages,<br />
such as 10 V DC. In conjunction with a transducer, voltages <strong>of</strong> up <strong>to</strong> 400 V can be pro-