1.2 Explanation of Relays<br />

Non−hold type relay and hold type relay<br />

There are two types of internal relays: hold type relays and non−hold type relays. When<br />

the power is turned off or the mode changed from RUN to PROG.,<br />

− Hold type relays hold their on or off status and resume operation in that status<br />

when the system is restarted.<br />

− Non−hold type relays reset.<br />

For the <strong>FP</strong>0 C10/C14/C16/C32, and <strong>FP</strong>−e without clock/calendar function, non−hold<br />

type and hold type relay numbers are as follows:<br />

Item Non-hold type Hold type<br />

<strong>FP</strong>0 C10, C14, C16<br />

<strong>FP</strong>−e<br />

R0 to R60F (976 points) R610 to R62F (32 points)<br />

<strong>FP</strong>0 C32 R0 to R54F (880 points) R550 to R62F (128 points)<br />

For the <strong>FP</strong>0 T32C/<strong>FP</strong>0R/<strong>FP</strong>Σ/<strong>FP</strong>−X/<strong>FP</strong>2/<strong>FP</strong>2SH/<strong>FP</strong>10SH, and <strong>FP</strong>−e with clock/<br />

calendar function, system register 7 can be used to specify whether a hold type or a<br />

non−hold type is used. If the beginning of a hold type relay is specified using a word<br />

number, relays before that point will be non−hold types, and subsequent relays will<br />

be hold types.<br />

Value of system register 7<br />

(initial number of hold type)<br />

Non-hold<br />

type<br />

Hold type<br />

Default settings for hold types and non−hold types<br />

Type Non−hold type Hold type<br />

<strong>FP</strong>10SH/<strong>FP</strong>2SH R0 to R499F (8000 points) R5000 to R886F (6192 points)<br />

<strong>FP</strong>2 R0 to R199F (3200 points) R2000 to R252F (848 points)<br />

<strong>FP</strong>0 T32C R0 to R9F (160 points) R100 to R62F (848 points)<br />

<strong>FP</strong>Σ R0 to R89F (1440 points) R900 to R97F (128 points)<br />

<strong>FP</strong>−e R0 to R60F (976 points) R610 to R62F (32 points)<br />

<strong>FP</strong>−X/<strong>FP</strong>0R R0 to R247F (3968 points) R2480 to R255F (128 points)<br />

Note<br />

For <strong>FP</strong>0R, <strong>FP</strong>Σ, <strong>FP</strong>−X and <strong>FP</strong>−e, in case of not using back−up<br />

battery, please keep the default value. Otherwise we cannot<br />

guarantee the function of hold/non−hold value.<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net<br />