1.1.6 <strong>FP</strong>2SH<br />

1.1 Table of Relays, Memory Areas and Constants<br />

Item Numbering Function<br />

Relay External input<br />

relay<br />

(X) 8,192 points (X0 to X511F) Turn on or off based on external input.<br />

Memory<br />

area<br />

External output<br />

relay<br />

Internal relay<br />

(* Note 1)<br />

Link relay<br />

(* Note 1)<br />

(Y) 8,192 points (Y0 to Y511F) Externally outputs on or off state.<br />

(R) 14.192 points (R0 to R886F) Relay which turns on or off only within program.<br />

(L) 10,240 points (L0 to L639F) This relay is a shared relay used for<br />

MEWNET link system.<br />

Timer (T) ( ) 3,072 , points p<br />

If a TM instruction has timed out, the con- con<br />

(* Notes 1 and 2)<br />

(T0 ( to T2999/ C3000 to C3071) ) tact with the same number turns on.<br />

Counter (C) ( ) If a CT instruction has counted up, the con- con<br />

(* Notes 1 and 2)<br />

tact with the same number turns on<br />

Pulse relay (P) 2,048 points (P0 to P127F) This relay is used to turn on only for one<br />

scan duration programmed with the OT"<br />

and OT# instructions.<br />

Error alarm relay (E) 2,048 points (E0 to E2047) If turned on while the unit is running, this<br />

relay stores the history in a dedicated buffer.<br />

Program this relay so that it is turned on at<br />

the time of abnormality.<br />

Special<br />

(R) 176 points (R9000 to R910F) Relay which turns on or off based on spe-<br />

internal relay<br />

cific conditions and is used as a flag.<br />

External input<br />

relay<br />

External output<br />

relay<br />

(WX) 512 words (WX0 to WX511) Code for specifying 16 external input points<br />

as one word (16 bits) of data.<br />

(WY) 512 words (WY0 to WY511) Code for specifying 16 external output<br />

points as one word (16 bits) of data.<br />

Internal relay (WR) 887 words (WR0 to WR886) Code for specifying 16 internal relay points<br />

as one word (16 bits) of data.<br />

Link relay (WL) 640 words (WL0 to WL639) Code for specifying 16 link relay points as<br />

one word (16 bits) of data.<br />

Data register<br />

(* Note 1)<br />

Link data register<br />

(* Note 1)<br />

Timer/Counter<br />

set value area<br />

(* Note 1)<br />

Timer/Counter<br />

elapsed value area<br />

(* Note 1)<br />

(DT) 10,240 words<br />

(DT0 to DT10239)<br />

Data memory used in program. Data is<br />

handled in 16-bit units (one word).<br />

(LD) 8,448 words (LD0 to LD8447) This is a shared data memory which is<br />

used within the MEWNET link system.<br />

Data is handled in 16-bit units (one word).<br />

(SV) 3,072 words<br />

(SV0 to SV3071)<br />

(EV) 3,072 words<br />

(EV0 to EV3071)<br />

Data memory for storing a target value of a<br />

timer and an initial value of a counter.<br />

Stores by timer/counter number.<br />

Data memory for storing the elapsed value<br />

during operation of a timer/counter. Stores<br />

by timer/ counter number.<br />

File register (FL) 98,295 , words Data memoryy used in program. p g Data is<br />

(* Note 1)<br />

(32,765 words ×3 banks ) hhandled dl d in i 16-bit 16 bit units it (one ( word). d)<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net<br />

1-17